Compaq 207590-B21 - Power Distribution Unit Strip Installation Instructions

Download Quick install manual of Compaq 207590-B21 - Power Distribution Unit Strip Other, Power Supply for Free or View it Online on All-Guides.com.

Compaq 207590-B21 - Power Distribution Unit Strip Quick install manual - Page 1
1
Compaq 207590-B21 - Power Distribution Unit Strip Quick install manual - Page 2
2
About This Device
1
3
3
1
1
3
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS - This Quick Installation Guide contains
important instructions for the rack-mounted PDU that should be followed during
installation.
This guide serves as an outline to assist qualified personnel with the installation
of the Compaq Power Distribution Unit (PDU).
The input voltage for this model PDU is 100VAC to 127VAC. This PDU
includes the following features:
Mounts in either 0U or 1U configuration, offering maximum flexibility for
utilizing rack space.
NOTE: 1U mounting kit sold separately (part number 215852-B21).
This model (207590-D71) provides 12 receptacles on 4 circuit breakers.
This PDU is used with UL listed and CSA certified information technology
equipment.
Installation is complete.
NOTICE
The information in this publication is subject to change without notice.
COMPAQ COMPUTER CORPORATION SHALL NOT BE LIABLE FOR
TECHNICAL OR EDITORIAL ERRORS OR OMISSIONS CONTAINED HEREIN,
NOR FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM
THE FURNISHING, PERFORMANCE, OR USE OF THIS MATERIAL. THIS
INFORMATION IS PROVIDED “AS IS” AND COMPAQ COMPUTER
CORPORATION DISCLAIMS ANY WARRANTIES, EXPRESS, IMPLIED OR
STATUTORY AND EXPRESSLY DISCLAIMS THE IMPLIED WARRANTIES OF
MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE, GOOD TITLE
AND AGAINST INFRINGEMENT.
This publication contains information protected by copyright. No part of
this publication may be photocopied or reproduced in any form without
prior written consent from Compaq Computer Corporation.
© 2000 Compaq Computer Corporation
Compaq, Registered U.S. Patent and Trademark Office.
COMPAQ POWER DISTRIBUTION UNIT KIT
QUICK INSTALLATION GUIDE FOR RACK-MOUNTED POWER DISTRIBUTION DEVICE
Second Edition (November 2000)
Part Number 215890-022
Compaq Computer Corporation
POWER DISTRIBUTION
UNIT KIT
Printed on recycled paper
Open Guide Completely Before
Beginning Installation Procedures
Quick Installation Guide for
Rack-Mounted Power Distribution Unit (PDU)
Low Voltage Model
Align bracket with screw holes in unit. Use screws 1 to attach brackets to the
sides of unit. Secure the unit to the side of rack by using screws 3 (two on each
side) to attach unit.
Please refer to the Important Safety Information (guide included with the PDU
kit) before installing this product.
Important Safety Information
Read Before Installing Product
The circuit breakers protect the PDU and all devices connected to it from
damage caused by an incoming electrical surge or equipment malfunction.
If power to a device is interrupted, check the circuit breakers and reset, if
necessary. If power is still not restored, contact your authorized Compaq service
representative at 1-800-OK-COMPAQ (1-800-652-6672). For continuous
quality improvement, calls may be recorded or monitored.
For additional information, visit the Compaq website at www.compaq.com.
About the Circuit Breakers
Kit Contents
Power Distribution Unit
Assembly, 0U mounting hardware
Mounting brackets - 0U (2)
Screws 1 mounting brackets to unit (6) [2 extra]
Screws 3 mounting unit to rack (6) [2 extra]
Cord retention hardware
Cord retention bracket
Screws 4 mounting bracket to unit (3) [1 extra]
Tie wraps (15) [several extra]
A ground bonding screw is provided on the rear of the unit as an attachment
point for conductors, should the rack contain any conductors used for the
purpose of grounding or bonding of ungrounded metal parts.
2
R
F
2
2
Align the bracket with screw holes in unit. Use screws 1 to attach brackets to
sides of unit. Slide unit into rails and secure by using screws 2 to attach unit.
2
2
1
1
Align the cord retention bracket with screw holes in unit. Use screws 4 to attach
bracket to the bottom of the unit.
2
Installing the Unit - 0U Configuration
4
Using the Ground Bonding Screw
Make sure the connected devices do not exceed capabilities of the unit.
This model has 12 receptacles, divided into 4 load groups. Each load group is
controlled by a 15A circuit breaker (12A derated) and contains 3 receptacles. This
model is rated at 24A total.
3
Installing the Unit - 1U Configuration
Connecting Devices
5
Installing the Cord Retention Bracket
1
4
4
NOTE: The 1U installation rack template, rails, and screws are included in the 0U / 1U
Installation kit, part number 215852-B21
(sold separately).
Regulatory Compliance Information
All regulatory certifications for this product were obtained under the following
agency series number. The corresponding part model number is shown.
207590-D71 EO3021
WARNING: There is a risk of personal injury from electrical
shock and hazardous energy levels. The installation of options
and routine maintenance and service of this product must be
performed by individuals who are knowledgeable about the
procedures, precautions, and hazards associated with AC power
products.
WARNING: To reduce the risk of personal injury resulting
from electric shock, do not remove the cover from the
Power Distribution Unit. There are no field-serviceable or
user-serviceable components inside.
Use 1U installation template to select and align rack mounting holes.
Place rear rail over the studs in the front rail . Tighten the nuts finger tight.
The mounting tab will be facing out, so the holes will align with the rack sides.
Adjust the length of rail assembly to fit inside rack. Tighten the nuts.
Insert the cage nuts (one on each side) in rack. Set hooks at rear of rail over
holes in rack. Use screws 2 (one on each side) to attach the rails to the rear of
the rack, through the cage nut. Use screws 2 (two on each side) to attach the
rails to the front of the rack.
R F