CREST AUDIO CC-STS Datasheet

Download Datasheet of Crest Audio CC-STS Other for Free or View it Online on All-Guides.com.

Brand: Crest Audio

Category: Other

Type: Datasheet for Crest Audio CC-STS

Pages: 2 (0.17 Mb)

Download Crest Audio CC-STS Datasheet

Crest Audio CC-STS Datasheet - Page 1
1
Crest Audio CC-STS Datasheet - Page 2
2
Product Information
The CC-STS module is the answer to system designers needs to
satisfy local building codes for emergency voice announcement
systems. These systems are typically referred to as “supervised”
installations where each amplifier senses a tone that is looped back
to the STS module. As a CC style module it is intended to operate in
a stand alone amplifier or can be used with NexSys local controllers
(LCP-AC8).
The CC-STS Module fits in the network bay located on the rear
panel of Crest Audio CK series of power processing amplifiers. The
module individually monitors each amplifiers output and the com-
plete speaker run for a pilot tone to ensure total system operation.
When the pilot tone is absent from the end of the speaker chain, the
Features
· Two independant speaker return inputs and two Alarm outputs A & B (contact closures)
· Works with any CC or NC type input module and CC type output module
· STS module resides in middle bay of the CK series amplifier
· Contact closures indicate loss of pilot tone or amplifier protect (amplifier output relays open) on either channel
· User selectable jumpers to enable normally open or normally closed contact closures
· Contact closures may be paralleled for a single return
· LED’s on the module indicate the type of fault
· Selectable tone sense range 13 to 30kHz. (Typical use is 20kHz.)
· User adjustable controls (recessed) for detector frequency and threshold level
· Provides continuous integrity monitoring (tone sense) required for many fire safety codes
· User selectable “Tone” fault enable / disable
· For use as a stand alone product (no network required) or with a local controller
Speaker Tone Sense Module
for CK series Power
Processing Amplifiers
unit sets a contact closure open or closed depending on your appli-
cation.
The module provides 2 inputs for speaker returns and two alarm
outputs (contact closures). The alarm outputs can be set to “Paral-
lel” or “Stereo” via the “Parallel Mode” jumper. In “Parallel” mode,
both alarm outputs trip when the pilot tone is absent on either (or
both) channel. In “Stereo” mode, each alarm operates indepen-
dently. Protect and Tone LED’s are also provided on the panel to
indicate which type of failure has occurred.
The CC-STS Modules are designed and manufactured in the United
States.
CC-STS connections
USA - Specificarion amplifier shown
Architects and Engineers Specifications - CC-STS
The module shall plug into the the middle bay of the CK Power Processing Se-
ries Amplifier. It will detect a pilot tone at the speaker return input. The
detectable frequency range of a the pilot tone will be between 13K to 30KHz.
The pilot tone frequency and threshold will be seletable by a recessed rear
panel potentiometer. The rear panel will have LED’s indicating a loss of
“Tone” or “Protect” fault for each channel. Two contact closures for“Alarm”
outputs are provided. There will be a user selectable jumper for independent
or paralled output operation. There will be a user selectable jumper for
“Tone” fault enable/disable.
LISTED 8B42
COMMERCIAL
POWER
AMPLIFIER
120V~60 Hz 15A
Speaker Return
Input
Ch A
Ch B
+–
+–
Thresh.
Freq.
Protect
Tone
Settings Faults
Model
CC-STS
Speaker Tone Sense Module
Contact
Closures
Alarm
Output
Crest Audio Inc.
100 Eisenhower Dr.
Paramus, New Jersey 07652 USA
www.crestaudio.com
Designed & manufactured in the USA by:
Ch A
Ch B
Input
Signal A
With
Pilot Tone
Speaker
Wire
Speaker
Wire
Speaker
Return
Wire
Speaker
Return
Wire
To Contact
Closure Input
To Contact
Closure Input
Input
Signal B
With
Pilot Tone
CC-STS