Warning
This instruction sheet only provides introductory information on electrical specification, installation and wiring.
Switch off the power before wiring. DO NOT touch any terminal when the power is switched on.
IFD9507 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key
or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
Introduction
Features
1. Auto-detects 10/100 Mbps transmission speed; MDI/MDI-X auto-detection.
2. The monitor table temporarily stores the monitored data for the user to fast save or acquire the data.
3. Supports Modbus TCP protocol and Ethernet/IP protocol (supports Master and Slave mode).
4. Able to send out emails after being triggered.
5. The station address, RS-485 communication format and baud rate can be set up externally.
6. The communication parameters can be set up through Web.
Product Profile & Outline
1
Communication ports: RS-485,
Ethernet, RS-232
2
Power indicator
3
Address switch
4
Data format/baud rate switch
5
Digit display
6
RS-485 indicator, Reset button,
Ethernet indicator
7
Module name
8
RS-485 connector, digital input
points, power input point, earth point
9
DIN rail connector
Specifications
Ethernet Interface
Interface RJ-45 with Auto MDI/MDIX
Transmission method Ethernet Type II
Transmission cable Category 5e, 100m (Max)
Transmission speed 10/100 Mbps Auto-Detection
Network protocol
ICMP, IP, TCP, UDP, DHCP, SMTP, M odbus OVER TCP/IP, Ethernet/IP, Delta
Configuration
ENGLISH
RS-485 Connector
Interface RJ-11
Transmission method RS-485
Transmission speed 110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200
Communication format Stop bit: 1, 2 Parity bit: None, Odd, Even Data bit: 7, 8 ASCII/RTU
Communication
protocol
Modbus, User Define
RS-232 Connector
Interface Mini Dim
Transmission method RS-232
Transmission speed 110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200
Communication format Stop bit: 1, 2 Parity bit: None, Odd, Even Data bit: 7, 8 ASCII/RTU
Communication
protocol
Modbus, Delta Configuration, User Define
Transmission cable DVPACAB215/DVPACAB230/DVPACAB2A30
Terminal Block
Interface Feed-through terminal 10PIN
Transmission method RS-485
Transmission distance 1,200m
Transmission speed 110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200
Communication format Stop bit: 1, 2 Parity bit: None, Odd, Even Data bit: 7, 8 ASCII/RTU
Communication
protocol
Modbus, User Define
Electrical Specifications
Power voltage 24V DC (-15% ~ 20%) supplied by feed-through terminal
Power consumption 3W
Insulation voltage 500V
Weight 140g
Environment
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz,
10V/m
Conducted Susceptibility Test (EN 61000-4-6, IEC 61131-2 9.10): 150kHz ~
80MHz, 3V/m
Surge Test (Biwave IEC 61132-2, IEC 61000-4-5):
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM
Operation/storage
Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage: -25ºC ~ 70ºC (tem perature), 5 ~ 95% (humidity)
Vibration/shock
immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC
68-2-27(TEST Ea)
Certificates
Installation
Dimension
Unit: mm
Address Switch
Switch setting Content
01 … F7 Valid Modbus communication address
Data Format Switch
Switch setting
Format
Switch setting
Format
0 7-N-1 8 7-N-2
1 8-N-1 9 8-N-2
2 7-O-1
A 7-O-2
3 8-O-1 B 8-O-2
6 7-E-1 E 7-E-2
7 8-E-1 F 8-E-2
Baud Rate Switch
Switch setting Baud rate (bps)
Switch setting Baud rate (bps)
1 110
7 4,800
2 150
8 9,600
3 300
9 19,200
4 600
A 38,400
5 1,200
B 57,600
6 2,400
C 115,200
RJ-11 PIN Definition
PIN Signal Definition
PIN Signal Definition
1 -- N/C
4 D- Negative pole for data
2 -- N/C
5 GND Ground
3 D+ Positive pole for data
6 -- N/C
RJ-45 PIN Definition
PIN Signal Definition
PIN Signal Definition
1 Tx+
Positive pole for data
transmission
5 -- N/C
2 Tx-
Negative pole for data
transmission
6 Rx-
Negative pole for data
receiving
3 Rx+
Positive pole for data
receiving
7 -- N/C
4 -- N/C
8 -- N/C
RS-232 PIN Definition
PIN Signal Definition
PIN Signal Definition
1 -- N/C
5 Tx Transmission data
2 -- N/C
6 -- N/C
3 -- N/C
7 -- N/C
4 Rx Reception data
8 GND Ground
Feed-through Terminal PIN Definition
PIN Signal Definition
1 SG Ground of signal
2 D- Data-
3 D+ Data+
4 X2 Digital input 2
5 X1 Digital input 1
6 X0 Digital input 0
7 S/S Ground of digital input
8 24V +24V
9 0V 0V
10 -- Earth ground
LED Indicators & Trouble-Shooting
There are 3 LED indicators and a digital display on IFD9507. POWER indicator displays the status of the
working power. RS-485 and LINK/ACT indicators display the connection status of the communication. The
digital display shows the address of and errors in IFD9507 and the error messages from the slave.
POWER LED
LED status Indication How to correct
OFF Working power is abnormal Check if the working power of IFD9507 is normal.
Green light ON
Working power is normal --
RS-485 LED
LED status Indication How to correct
OFF
No communication or RS-485
connection is abnormal.
1. If the LED is off during the communication, check if the RS-
485 in
IFD9507 is normally connected.
2. Check at least 1 node on the network is communicating normally.
Constantly ON
Abnormal RS-485 connection Switch D+ and D-
Green light
flashes
RS-485 connection is normal. --
LINK/ACT LED
LED status Indication How to correct
OFF
No power, or no network
connection
1. Check the power of IFD9507 and make sure the network
connection is normal.
2. Re-power IFD9507. If the error still exists, send your IFD9507
back to the factory for rep ir.
Green light ON
The connection is normal, but no
data transmission.
--
Green light
flashes
The data transmission is normal.
--
Codes in Digital Display
Code Indication How to correct
01 ~ F7
The node address of IFD9507 when
in normal operation
--
F0 Returning to default setting --
F1 IFD9507 is booting. --
F2 Working power in low voltage Check if the working power is normal.
F3 Internal memory error
1. Re-power IFD9507. If the error still exists, try step 2.
2. Reset IFD9507. If the error still exists, send it back to the factory
for repair.
F4
Internal error caused by
manufacturing in the factory
1. Re-power IFD9507. If the error still exists, try step 2.
2. Reset IFD9507. If the error still exists, send it back to the factory
for repair.
F5 Network connection error Check if IFD9507 is normally connected to the network.
F6
Full number of devices connected in
the network
Check if the number is too much.
F7 UART setting error. Check if the RS-485, RS-232 communication format is correct.
E1 Alarm 1 triggered Check Alarm Input Point 1
E2 Alarm 2 triggered Check Alarm Input Point 2
E3 Alarm 3 triggered Check Alarm Input Point 3
01 Incorrect Modbus function Check if the Modbus instruction is correct.
02 Incorrect address Check if the Modbus instruction is correct.
03 Incorrect data Check if the Modbus instruction is correct.
04 CRC error
1. Check if IFD9507 and RS-485 is connected normally.
2. Check if the series transmission speed is consistent with that of
other nodes on the network.
0B No response from the station
1. Check if IFD9507 and RS-485 is connected normally.
2. Check if the series transmission speed is consistent with that of
other nodes on the network.
(OPEN TYPE)
1. 10/100 Mbps MDI/MDI-X
2.
Monitor table
3. Modbus TCP Ether net/IP ( Master Slave )
4.
5. RS-485
6. Web
1
RS-485, Ethernet,
RS-232
2
3
4
5
6
RS-485 Reset
Ethernet
7
8
RS-485
9
DIN
Ethernet
RJ-45 with Auto MDI/MDIX
Ethernet Type II
Category 5e, 100 (Max)
10/100 Mbps Auto-Detection
ICMP, IP, TCP, UDP, DHCP, SMTP, Modbus OVER TCP/IP, Ethernet/IP, Delta
Configuration
RS-485
RJ-11
RS-485
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200
Stop bit: 1, 2 Parity bit: None, Odd, Even Data bit: 7, 8 ASCII/RTU
Modbus, User Define
RS-232
Mini Dim
RS-232
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200
Stop bit: 1, 2 Parity bit: None, Odd, Even Data bit: 7, 8 ASCII/RTU
Modbus, Delta Configuration, User Define
DVPACAB215/DVPACAB230/DVPACAB2A30
10PIN
RS-485
1,200m
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200
Stop bit: 1, 2 Parity bit: None, Odd, Even Data bit: 7, 8 ASCII/RTU
Modbus, User Define
24V DC (-15% ~ 20%)
3W
500V
140g
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m
Conducted Susceptibility Test (EN 61000-4-6, IEC 61131-2 9.10): 150kHz ~ 80MHz,
3V/m
Surge Test (Biwave IEC 61132-2, IEC 61000-4-5):
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM
0ºC ~ 55ºC 50 ~ 95% 2
-25ºC ~ 70ºC 5 ~ 95%
IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST
Ea)