Delta Electronics Communication Module RTU-485 Instruction Manual

Download Instruction sheet of Delta Electronics Communication Module RTU-485 Switch for Free or View it Online on All-Guides.com.

Delta Electronics Communication Module RTU-485 Instruction sheet - Page 1
1
Delta Electronics Communication Module RTU-485 Instruction sheet - Page 2
2
5011668000-R U00
2007-08-13
Warning
Please read this instruction sheet carefully before use.
Switch off the power before wiring.
RTU-485 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required to open the enclosure) in case danger and damages on the
device may occur.
DO NOT touch the internal circult in one minute after the power is switched off.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur.
Check all the wiring again before switching on the power and DO NOT touch any terminal when the power is
switched on. Make sure the ground terminal is correctly grounded in order to prevent electromagnetic
interference.
Introduction
Thank you for choosing Delta RTU-485 communication module. RTU-485 is a Modbus remote I/O
communication module for Delta's PLC to remote-control Slim series DI/DO and AI/AO extension units.
As a standard Modbus slave, RTU-485 is compatible with other master station complying with Modbus
protocol.
Product Profile & Outline
SG D- D+
STOP
RUN
RTU-485
RUN
ALAR M
POW ER
RS-4 85
1
2
3
5
6
9
8
7
4
10
11
12
13
14
15
16
Unit: mm
1. POWER indicator 9. Mounting hole for extension unit
2. RUN indicator 10. Nameplate
3. ALARM indicator 11. Extension port for extension unit
4. RUN/STOP switch 12. DIN rail slot (35mm)
5. Communication indicator 13. Fastening hole for extension unit
6. Address setup DIP switch 14. DIN rail clip
7. Communication mode setup DIP switch 15. Mounting rail for extension unit
8. RS-485 communication port 16. Power input
ENGLISH
Specifications
RTU-485 Connector
Type Removable 3-pin connector
Transmission
method
RS-485
Transmission cable 2 twisted isolation cables
Electrical isolation 500V DC
Communication
Valid communication
address
1 ~ F0 (decimal: 1 ~ 240)
Series transmission
speed
1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps (bits per second)
Communication
mode
7,E,1-ASCII / 7,O,1-ASCII / 7,E,2-ASCII / 7,O,2-ASCII / 7,N,2-ASCII / 8,E,1-ASCII /
8,O,1-ASCII / 8,N,1-ASCII / 8,N,2-ASCII / 8,E,1-RTU / 8,O,1-RTU / 8,N,1-RTU/
8,N,2-RTU
Electrical Specification
Power voltage 24V DC (-15% ~ 20%) (with DC input polarity reverse protection)
Environment
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge, 4KV Contact Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Li4ne: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz , 1.4GHz ~ 2.0GHz , 10V/m
Operation/storage
Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage: -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity)
Shock/vibration
immunity
International standards: IEC61131-2 IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27
(TEST Ea)
Standards IEC 61131-2, UL508
Components
RUN/STOP Switch
Status Explanation
1. RUN indicator on RTU-485 is On.
2. AI/AO extension unit in RUN status.
1. AI/AO extension unit switches from RUN to STOP status.
RUN STOP
2. Y points on DI/DO extension unit are all Off.
1. RUN indicator on RTU-485 is Off.
2. AI/AO extension unit in STOP status.
3. Communication control is not allowed in AI/AO extension unit.
STOP
4. Communication control is not allowed in DI/DO extension unit.
1. RTU-485 re-detects the number of points in DI/DO unit and the
number of AI/AO units.
ST OP
RU N
STOP RUN
2. AI/AO extension unit switches from STOP to RUN status.
Address Setup DIP Switch
DIP Switch Setting Explanation
H’01 ~ H’F0
For valid RTU-485 address, the definition of ID0 ~ ID7
are: 2
0
, 2
1
, 2
2
, … 2
6
, 2
7
.
H’00, H’F1 ~ H’FF
In the Modbus protocol, H’00 is defined as broadcast
mode. H’F1 ~ H’FF are incorrect RTU-485 addresses.
Communication Mode Setup DIP Switch
The communication setup switch is a set of 8-bit DIP switches. PA0 ~ PA3 are for setting up RTU-485
communication mode, DR0 ~ DR2 are for setting up the series transmission speed, and A/R is for setting
up ASCII/RTU mode. There are 13 communication modes and 8 series transmission speeds available.
PA3 PA2 PA1 PA0 A/R Communication mode
OFF OFF OFF OFF ON 7,E,1-ASCII
OFF OFF OFF ON ON 7,O,1-ASCII
OFF OFF ON OFF ON 7,E,2-ASCII
OFF OFF ON ON ON 7,O,2-ASCII
OFF ON OFF OFF ON 7,N,2- ASCII
OFF ON OFF ON ON 8,E,1-ASCII
OFF ON ON OFF ON 8,O,1-ASCII
OFF ON ON ON ON 8,N,1-ASCII
ON OFF OFF OFF ON 8,N,2-ASCII
OFF ON OFF ON OFF 8,E,1-RTU
OFF ON ON OFF OFF 8,O,1-RTU
OFF ON ON ON OFF 8,N,1-RTU
ON OFF OFF OFF OFF 8,N,2-RTU
Other settings of PA3, PA2, PA1, PA0 and A/R will be regarded as invalid
communication modes
DR2 DR1 DR0 Series Transmission speed
OFF OFF OFF 1,200 bit/s
OFF OFF ON 2,400 bit/s
OFF ON OFF 4,800 bit/s
OFF ON ON 9,600 bit/s
ON OFF OFF 19,200 bit/s
ON OFF ON 38,400 bit/s
ON ON OFF 57,600 bit/s
ON ON ON 115,200 bit/s
Function Codes Supported by RTU-485
RTU-485 complies with the standard Modbus protocol, supporting the 7 function codes, H’01, H’02, H’03,
H’05, H’06, H’0F, and H’10. Please refer to the standard Modbus protocol for the specific data format of
each function code.
Function code
Function Data type Applicable address
H’01
Read the output status of bit
device
bit DO area: H’0500 ~ H’057F
H’02
Read the input status of bit
device.
bit DI area: H’0400 ~ H’047F
Special function area: H’0000 ~ H’001F
CR of the 1
st
AI/AO unit: H’1600 ~ H’1630
CR of the 2
nd
AI/AO unit: H’1640 ~ H’1670
CR of the 3
rd
AI/AO unit: H’1680 ~ H’16B0
CR of the 4
th
AI/AO unit: H’16C0 ~ H’16F0
CR of the 5
th
AI/AO unit: H’1700 ~ H’1730
CR of the 6
th
AI/AO unit: H’1740 ~ H’1770
CR of the 7
th
AI/AO unit: H’1780 ~ H’17B0
H’03 Read register word
CR of the 8
th
AI/AO unit: H’17C0 ~ H’17F0
H’05
Write single datum into bit
device
bit DO area: H’0500 ~ H’057F
RUN/STOP RTU module: H’0003
H’06 Write single datum into register word
Applicable to CR with write attribute in the 1
st
~ 8
th
AI/AO extension unit.
H’0F Write many data into bit device bit DO area: H’0500 ~ H’057F
RUN/STOP RTU module: H’0003
H’10 Write many data into register word
Applicable to CR with write attribute in the 1
st
~ 8
th
AI/AO extension unit.
Example: Use function code 03 to read CR0 and CR1 in the 1
st
AI/AO extension unit: (ASCII mode)
The request message sent from master PLC to RTU-485 is “: 01 03 16 00 00 02 E4 CR LF”
The responding message sent from RTU-485 to the master PLC is “: 01 03 04 00 88 00 00 70 CR LF”
Note:
1. RTU-485 can only read and write one AI/AO extension unit at the same time.
2. RTU-485 is able to read/write maximum 16 words at a time in the communication control.
LED Indicators
POWER Indicator
LED status Indication How to deal with it
Off No power
Check if the power and connection of
RTU-485 work normally. If both work
normally, your RTU-485 malfunctions.
Please change to a new RTU-485.
Constantly On in green RTU-485 module is powered -
RUN Indicator
LED status Indication How to deal with it
Off
RTU-485 and the connected AI/AO
extension unit are in STOP status.
-
Constantly On in green
RTU-485 and the connected AI/AO
extension unit are in RUN status.
-
ALARM Indicator
LED status Indication How to deal with it
Red light flashes Low power voltage
Adjust the voltage supplied to RTU-485 to
normal voltage.
Incorrect communication format
Reset to the communication format
supported by RTU-485 and re-power the
module after the setup.
Incorrect station No.
Check if the station No. is within H’01 ~
H’F0.
Constantly On in red
1. No extension unit connected
2. More than 8 extension unit
connected
3. More then 128 I/O points in the
extension unit.
1. Make sure the extension unit is correctly
connected.
2. Make sure the number of connected
extension units is less than 8.
3. Make sure the number of I/O points is
less than128.
RS-485 Indicator
LED status Indication How to deal with it
Red light flashes during
communication
The LED will flash once when RTU-485
and the master completes the
communication of 1 message.
-
OPEN TYPE
RTU-485 RTU-485 Modbus I/O
Slim DI/DO AI/AO RTU-485 Modbus
Modbus
SG D- D+
STOP
RUN
RTU-485
RUN
ALAR M
POW ER
RS-4 85
1
2
3
5
6
9
8
7
4
10
11
12
13
14
15
16
mm
1. POWER 9.
2. RUN 10.
3. ALARM 11.
4. RUN/STOP 12. DIN (35mm)
5. Communication 13.
6. 14. DIN
7. 15.
8. RS-485 16.
RTU-485
3Pin
RS-485
2
500V DC
1 ~ F0 1 ~ 240
1,200 2,400 4,800 9,600 19,200 38,400 57,600 115,200 bps /
7,E,1-ASCII 7,O,1-ASCII 7,E,2-ASCII 7,O,2-ASCII 7,N,2-ASCII 8,E,1-ASCII 8,O,1-ASCII
8,N,1-ASCII 8,N,2-ASCII 8,E,1-RTU 8,O,1-RTU 8,N,1-RTU 8,N,2-RTU
24V DC (-15% ~ 20%)
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 4KV Contact Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz~1000MHz , 1.4GHz~2.0GHz , 10V/m
/
0ºC ~ 55ºC 50 ~ 95% 2
-25ºC ~ 70ºC 5 ~ 95%
/ IEC61131-2 IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
IEC 61131-2 UL508
RUN/STOP
1. RTU-485 RUN
RUN
2. AI/AO RUN
1. AI/AO RUN STOP
RUN STOP
2. DI/DO Y OFF
1. RTU-485 RUN
2. AI/AO STOP
3. AI/AO
STOP
4. DI/DO
1. RTU-485 DI/DO AI/AO
S TOP
RU N
STOP RUN
2. AI/AO STOP RUN