Ei Electronics Heat Alarm Ei 103R Brochure

Download Technical specifications of Ei Electronics Heat Alarm Ei 103R Smoke Alarm for Free or View it Online on All-Guides.com.

Ei Electronics Heat Alarm Ei 103R Technical specifications - Page 1
1
Ei Electronics Heat Alarm Ei 103R Technical specifications - Page 2
2
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei103R DataSht RevA
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Web: www.eielectronics.com
Model Ei 103R Heat Alarm
Fixed temperature fast response thermistor type
sensor, range 54°C to 62°C
Supply voltage 10.2 to 14 volts
Test button
Interconnect up to 12 alarms
Relay contacts
Built in sounder
Automatic reset facility
Kitemarked to BS5446-1:2000
5 year guarantee
Product Description
The Ei103R is a Heat Alarm that is designed to operate
with suitable 12 volt control panel and to provide a loud
local alarm.
Relay contacts (normally open and closed supplied) are
available for triggering the panel itself and its associated
ancillary products, such as extra loud sirens, magnetic
door holders etc.
The Ei103R is easily installed and comes supplied with
all necessary screw fixings..
The Ei103R has advanced features such as the ability to
interconnect up to twelve alarms to allow all alarms to
sound if just one of the interconnected alarms should be
triggered.
The Ei103R is ideal for use in kitchens and garages,
where the use of optical or ionisation alarms would lead
to unwanted nuisance alarms.
On escape routes this alarm must be interconnected
with smoke alarms.
Operation
The alarm will activate the built in sounder upon
detecting heat that reaches 58ºC
The heat alarm will automatically reset itself and
silence the sounder when the temperature drops
below the preset level.
The built in sounder will provide a minimum sound
output of 85dB at 3m
The “Test” button will simulate the effect of heat
and tests sensor, electronics and horn
Interconnect up to 12 other alarms (9V ionisation,
optical or heat) when one senses smoke, all alarm.
Helps ensure warning will be heard throughout the
house
WITH RELAY FEATURE