SERIES MAX INDUSTRIAL STROBES
INSTALLATION INSTRUCTIONS
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock's Series Max Strobes are UL 1638 Listed for indoor or outdoor use. They are high intensity visible warning
appliances that are designed for use in either stationary locations or mobile equipment. All Series Max Strobes are weather-
resistant. They produce a powerful double flash light burst at the rate of 60 double flashes per minute. Series Max Strobes can
be installed using 1/2-inch pipe mount, surface mount or flange mount (an integral 1/2-inch pipe thread, a flange mounting ring
and a weather-resistant gasket are included with each unit). They can also be mounted to standard 4-inch square electrical boxes,
100mm European boxes and Wheelock's WBB outdoor box. There are four models of Series Max Strobes: The AC-MAX and
AC-MAXS Models for 120VAC applications and the DC-MAX and DC-MAXS Models for use with any DC voltage from
10.5VDC to 31.0VDC. The AC-MAX and DC-MAX are strobe only models while the AC-MAXS and DC-MAXS models offer
a steady-light feature along with the strobe operation. All models are available with either clear, amber, red, or blue lens color.
NOTE
: All
CAUTIONS
and
WARNINGS
are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE
FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD
RESULT IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1A: Ratings per UL
Model
Code
Lens
Color
Minimum
Voltage
Rated
Voltage
Maximum
Voltage
Input
Current
Flash
Rate
AC-MAX-A
AC-MAXS-A
Amber
AC-MAX-B
AC-MAXS-B
Blue
AC-MAX-C
AC-MAXS-C
Clear
AC-MAX-R
AC-MAXS-R
Red
102
VAC
120
VAC
127
VAC
0.20A @
120VAC
60/Min
Typ.
DC-MAX-A
DC-MAXS-A
Amber
DC-MAX-B
DC-MAXS-B
Blue
DC-MAX-C
DC-MAXS-C
Clear
DC-MAX-R
DC-MAXS-R
Red
10.5-31.0
VDC
1227mA @ 10.5VDC
1010mA @ 12VDC
470mA @ 24VDC
344mA @ 31VDC
60/Min
Typ.
Table 1B: Steady-light Specifications
Model Code Rated Voltage Current mA
AC-MAXS 120VAC 120mA
DC-MAXS 10.5-31.0VDC 665mA
NOTES:
1. Temperature range for all models is -31°F to +151°F (-35°C to +66°C)