- 1 -
VINO1500SS
VINO1900SS
Installation Instruction
Federal law requires that WINEMATE split cooling systems be
installed by an EPA certified refrigeration technician.
1. Location
• Place the condensing unit in a properly ventilated location. If it is not, heat
exhausted by the condensing unit will build up and the cooling system will
not operate properly.
• Leave minimum 3 feet clearance between the exhaust side and the wall.
• Leave minimum 1 foot clearance for the fresh air supply side.
• Condensing unit should be elevated to avoid possible flooding and shaded
from direct sun. It should not be exposed to temperatures higher than 125
°F or lower than 20 °F.
• Air flow from the unit cooler should be unobstructed for at least 1 foot.
2. Refrigeration Installation
Model Liquid Line Diameter
(inch), recommended
Suction Line Diameter
(inch), recommended
VINO1500SS 1/4 3/8
VINO1900SS 1/4 3/8
WINEMATE split system is shipped as components and is ready for use only
after a certified refrigeration technician has properly installed and tested the
system. Proper installation is critical. WINEMATE can only warrant the quality of