Midplane assembly replacement 70
Step Midplane assembly replacement action and verification
Step 1 Action
Contact an authorized service provider to perform the following steps:
1 Power down all server blades.
2 Disconnect power from the enclosure.
3 Remove all devices from all device bays. Be sure to note the location for each
device.
4 Remove all interconnect modules.
5 Remove all fans.
6 Remove all Onboard Administrators from the enclosure.
7 Remove the OA tray.
8 Remove the rear cage.
9 Remove the midplane assembly.
10 Install a service spare midplane assembly.
11 Install the rear cage.
Step 2 Action
1 Install following components in their original locations in the enclosure:
• Power supplies
• Fans
• Onboard Administrator
• OA tray
2 Power up the enclosure.
Verification
When the Insight Display indicates that the Onboard Administrator has completed all
power-on tests, continue to the next step.
Step 3 Action
Update the PID and serial numbers:
1 Locate the enclosure label on the front left mounting tab.
2 Record the enclosure PID and serial number.
3 Log in to OA CLI using the Administrator account.
4 Update the enclosure part number using the following OA CLI command. In place of
X, enter the PID number.
set enclosure part_number X
5 Update the enclosure serial number using the following OA CLI command. In place
of X, enter the serial number.
set enclosure serial_number X
Verification
If troubleshooting the HP BladeSystem c3000 Enclosure, then continue to step 5.
If troubleshooting the HP BladeSystem c7000 Enclosure, then continue to the next step.