Honeywell P520 Specifications

Download Specifications of Honeywell P520 Processor for Free or View it Online on All-Guides.com.

Brand: Honeywell

Category: Processor

Type: Specifications for Honeywell P520

Pages: 16 (1.24 Mb)

Download Honeywell P520 Specifications

Honeywell P520 Specifications - Page 1
1
Honeywell P520 Specifications - Page 2
2
Honeywell P520 Specifications - Page 3
3
Honeywell P520 Specifications - Page 4
4
Honeywell P520 Specifications - Page 5
5
Honeywell P520 Specifications - Page 6
6
Honeywell P520 Specifications - Page 7
7
Honeywell P520 Specifications - Page 8
8
Honeywell P520 Specifications - Page 9
9
Honeywell P520 Specifications - Page 10
10
Honeywell P520 Specifications - Page 11
11
Honeywell P520 Specifications - Page 12
12
Honeywell P520 Specifications - Page 13
13
Honeywell P520 Specifications - Page 14
14
Honeywell P520 Specifications - Page 15
15
Honeywell P520 Specifications - Page 16
16
USER MANUAL
Put Bar Code Here
66-2066-01
P520 Signal Processor
APPLICATION
The Honeywell P520 is a rack mounting signal processor that
is compatible with viewing heads in the S5XX and S55XB/BE
series. These include models S506, S509, S511 and S512,
and the advanced viewing head series models S550B/BE,
S552B/BE and S556B/BE. There is only one model of the
P520 available, which is DC powered. A rear backplane PC
Board is required for termination (order part number
REARPCB separately for initial installation).
FEATURES
Rack mounted system, designed to conform to the DIN
41494 19 inch card frame system
3U high and 21HP wide, or 5.06 x 4.18 inches with a
length of 8.66 inches (220mm)
Once rack mounted, together with a power supply and
appropriate viewing head makes up a complete flame
monitoring system
SPECIFICATIONS
Electrical Ratings
Input Power: 22 - 26VDC, 130mA (plus 100mA for each
Viewing Head.)
Battery Backup: 24VDC, 130mA (plus 100mA for each
Viewing Head.) Main Voltage > Battery Voltage
Ambient Temperature:
0°C to 52°C (32°F to 125°F) CSA Rating
0°C to 60°C (32°F to 140°F) FM Rating
Outputs:
Flame Relay: 2 Form C Contacts (DPDT)
Self-Checking Relay: 1 Form C Contact (SPDT)
Contact Ratings: 5A at 30 VDC, 125 VAC and 277 VAC
Max switching voltage 220Vdc, 250Vac
Analog Flame Signal: 0 to 19.8mA current output for
remote meters and 4 to 19.8mA output. (360 ohm max.
resistance.)
Power to Viewing Head:
+26VDC maximum, fused 0.25A (self-resetting)
+14.3VDC pulsing 0.2 seconds ON, 0.8 seconds OFF
Inputs:
Channel Select (Isolated Input):
7.5-30VDC range
Input resistance 3900 ohms
26VDC maximum, 6.4mA
10VDC, 2.3mA
Flame Signal from Viewing Head (Isolated Input):
7.5-30VDC range
Input resistance 3900 ohms
13.6VDC, 3.2mA
Serial Communications:
RS-422 (Differential)
4800 or 9600 baud (user selected)
4 wire / 2 twisted pair
Cable (between viewing head and signal processor):
4 conductor, #16 AWG or #18 AWG, one wire shielded with
braided shield for flame signal. Honeywell C328 cable is
recommended.