ABuilding Safety. Building Security.
Extinguishing Control Panel
BC06-1EXT, BC06-2EXT
For application in single-zone
extinguishing systems
4 detector zones in conventional
technology
Differentiation between the activation
of automatic detectors and manual
call points on the same detector line
Clear display and operation on the
panel front
Tested to EN 54-2, -4, EN 12094-1 by
VdS
Already in the basic version the combined Fire/Extingu-
ishing Control Panels BC06-1EXT and BC06-2EXT are
equipped with four detector lines and the Extinguishing
Board EXB1-1 and, owing to its sophisticated factory
settings, are immediately ready for operation. This al-
lows for quick and effi cient application of the product.
The conventional technology allows for the connection
of automatic and non-automatic re detectors as well
as a wide range of special detectors with contact out-
put. Alarms from manual call points and from automatic
detectors that are connected together to one detector
line can be differentiated and thus evaluated differently
by the re/extinguishing control panel, by means of an
optional coding module.
Thanks to the two auxiliary inputs whose parameters
can be freely set as well as the eight open-collector out-
puts, manifold tasks in the eld of re alarm technology
can be realised.
The optional evacuation function serves for the actu-
ation of alarming devices independent from activated
alarms.
Thanks to the integrated extinguishing module, the
BC06 can be used as an extinguishing control panel
according to EN 12094-1 with one ooding zone. The
module provides appropriate inputs and outputs for con-
trolling and monitoring a fl ooding zone. The display and
operating elements that are necessary for the status
indication and the operation of the extinguishing module
are integrated into the keypad.
A printer for the event log can be connected via the
optional Serial Interface Modul SIM06-1.
The Fire/Extinguishing Control Panel BC06-2EXT dif-
fers from the BC06-1EXT by the additionally integrated
4-digit electronic alarm counter.
Fire is a permanent threat to life and property. There-
fore, immediate response to a re is imperative. The
main objective of the Fire Detection Control Panel
Series BC06 is to alarm and to react in time and, con-
sequently, save lives and protect property. For decades
LST have focused their aims to undertaking unrivaled
efforts in order to realise new innovations in the security
area. Research, development and production are loca-
ted within LST premises, thus guaranteeing fl exible and
reliable individual solutions.
Using a powerful processor system and a large number
of integrated functions, the Fire/Extinguishing Control
Panels Series BC06 ensure topmost effi ciency and
speed – prerequisites for saving lives and minimising
damage to property.
Description