Maytag POF1HD140AVFA Installation, Operation And Maintenance Manual

Download Installation, operation and maintenance manual of Maytag POF1HD091AVFA Furnace for Free or View it Online on All-Guides.com.

Brand: Maytag

Category: Furnace

Type: Installation, operation and maintenance manual

Model: Maytag POF1HD091AVFA , Maytag POF1HD140AVFA

Pages: 36

Download Maytag POF1HD091AVFA Installation, operation and maintenance manual

Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 1
1
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 2
2
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 3
3
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 4
4
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 5
5
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 6
6
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 7
7
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 8
8
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 9
9
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 10
10
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 11
11
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 12
12
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 13
13
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 14
14
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 15
15
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 16
16
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 17
17
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 18
18
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 19
19
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 20
20
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 21
21
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 22
22
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 23
23
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 24
24
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 25
25
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 26
26
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 27
27
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 28
28
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 29
29
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 30
30
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 31
31
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 32
32
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 33
33
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 34
34
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 35
35
Maytag POF1HD091AVFA Installation, operation and maintenance manual - Page 36
36
A.1 OIL BURNER AIR ADJUSTMENT
The burner air supply is adjusted to maintain the fuel to
air ratio to obtain ideal combustion conditions. A lack of
air causes "soft" and "sooty" flames, resulting in soot
build-up throughout the heat exchanger passages.
Excess combustion air causes a bright roaring fire and
high stack temperatures resulting in poor fuel
efficiency. The POF1HD140AVFA and
POF1HD091AVFA furnaces operate most efficiently
with a No. 1 smoke spot on the Bacharach Scale. This
is not necessarily the optimum setting; however,
because dust will inevitably build up on the air moving
components of the oil burner assembly. This will result
in decreased air supply with the potential result of soot
building up in the flue gas passageways of the heat
exchanger. Soot behaves as an insulator and impairs
good heat transfer. Stack temperature will increase,
and the overall efficiency will decrease. As a means of
avoiding this problem, it is advisable to adjust the air
supply to provide no more than a trace smoke spot on
the Bacharach Scale.
For complete details, consult the oil burner instruction
manual provided in the furnace documents envelope.
Beckett AF Burner
Adjust the air shutter by loosening the locking screws
and moving the air shutter, and if necessary, the bulk
air band.
A.2 BURNER ELECTRODES
Adjustment of the electrode tips with respect to each
other, the nozzle, and to the rest of the burner is very
important to ensure smooth start-ups and to permit
efficient combustion.
Beckett AF Burner
Electrode gap: 5/32 inch.
Distance above horizontal centerline: 5/16 inch. Older
instruction sheets specify 7/16 inch. The current
specification is 5/16 inch.
Distance ahead of nozzle: 1/16 inch.
“Z” dimension, the distance from the front of the end
cone (head) to the face of the nozzle should be 1-1/8
inches. If a ceramic head is used, the distance from
the end cone to the nozzle face is increased to 1-3/8
inches.
A.3 START UP
The furnace should be operated for a minimum of 10
minutes to reach steady state conditions before fine
tuning combustion. The warm up time is ideal for
testing the oil pump pressure.
Drill a 1/4-inch test port in the venting between the
furnace flue outlet and draft regulator (barometric
damper). Insert a stack thermometer and note the flue
gas temperature. The flue gases should be within a
range of 350°F to 450°F. If the flue gases are below
the range, it may be necessary to slow down the
blower fan. If the flue gases are above the range, the
blower fan may require speeding up. Stack
temperature varies directly with the system
temperature rise. System temperature rise is the
difference between the furnace outlet temperature and
furnace inlet temperature as measured in the vicinity of
the connection between the plenum take-offs and the
trunk ducts. Temperature rise value is listed on the
system rating plate.
Perform a smoke spot test. The smoke spot should not
exceed No. 1 on the Bacharach Scale.
After the air adjustments have been completed, re-
check the draft pressure at the test port on the burner
mounting plate as shown in Figure 2. The draft should
be adjusted to -0.02 inches w.c.
In the United States, the Beckett AF Burner may be
equipped with Beckett's "Inlet Air Shut-Off" to increase
efficiency. (Beckett Part No. AF/A 5861).
NOTE: USE OF THE INLET AIR SHUT-OFF
COULD CAUSE POST COMBUSTION NOZZLE
DRIP.