42
BIOS Battery: Lithium Coin Cell #BR2032, 3 Volts/190mA, 20mm
Diameter x 3.2mm height.
CAUTION, Battery may explode if mistreated. Do not recharge,
disassemble or dispose of in fire.
CAUTION: Risk of Explosion if battery is replaced by an incorrect type.
Dispose of used batteries according to local disposal jurisdiction."
Maximum Surrounding Air Temperature: -30C to +75C, T-Code: T3C
Relative Humidity: 5-95% Non-Condensing.
Storage Temperature: -40C to 85C.
Non-Isolated: Power and field commons have a direct electrical
connection.
Shock & Vibration Immunity: Surface mounted unit with all cables
attached except USB Ports 3 and 4
Sinusoidal Vibration: IEC 60068-2-6: 10-500 Hz, 5G, 2 Hours/axis
Random Vibration: IEC 60068-2-64: 10-500 Hz, 5G-rms, 2 Hours/axis
Operating Shock: IEC 60068-2-27:
30g, 11 ms half sine, 18 shocks at 6 orientations
50g, 3ms half sine, 18 shocks at 6 orientations
Agency Approvals: FCC Class A, CE (EMC Directive 2004/108/EC).
Electromagnetic Interference Immunity (EMI): Inputs/outputs have
demonstrated resistance to inadvertent state changes with interference
from switching solenoids, commutator motors, and drill motors.
Electromagnetic Compatibility (EMC) -
Minimum Immunity per European Norm EN61000-6-2:2001
Electrostatic Discharge (ESD) Immunity: 4KV direct contact and 8KV
air-discharge to the enclosure port per IEC61000-4-2.
Radiated Field Immunity (RFI): 10V/M, 80 to 1000MHz AM and
900MHz keyed carrier, per IEC61000-4-3.
Electrical Fast Transient Immunity (EFT): 2KV to power, and 1KV to
signal I/O per IEC61000-4-4.
Conducted RF Immunity (CRFI): 10Vrms, 150KHz to 80MHz, per
IEC61000-4-6.
Surge Immunity: 0.5KV to power per IEC61000-4-5. By the standard,
this test is not applicable to DC power input ports intended to be
permanently connected to cables less than 10m in length. Further,
this test is not applicable to I/O ports that interface via cables whose
total length is less than 30m.
BIOS Battery Back-up
ENVIRONMENTAL
WARNING: - Explosion
Hazard – Do not disconnect
equipment unless power has
been removed or the area is
known to be non-hazardous.
WARNING: - The area must
be known to be non-
hazardous before servicing
/replacing the unit and before
installing.