INSTALLATION INSTRUCTIONS Model TCB-EXS21TLE
INFORMATION FOR THE PERSON IN CHARGE OF INSTALLATION (ELECTRICAL) WORK AND SERVICING
(E)
Safety Precautions
Read these Safety Precautions before beginning installation or electrical work, and
perform the work only in the correct manner.
Precautions in this manual are given in the form of “Warnings” or “Cautions.” Both types
of precautions contain important information related to your safety, the safety of users,
and the correct operation, installation, or maintenance of the air conditioning system. Be
sure to carefully observe all relevant precautions.
When installation work is completed, perform a test run and check that no trouble occurs.
Also be sure to explain the methods for using the product to the customer, based on the
contents of the Operation Manual. In addition, request that the customer keep and
conveniently store the “Information for the Person in Charge of Installation (Electrical) Work
and Servicing” together with the Operation Manual.
Request installation and electrical work only from the dealer or a qualified air
conditioning specialist.
Attempting to carry out installation work on your own, and doing so incorrectly, may
result in electrical shock, fire, or other hazards.
Installation procedures must be performed correctly, carefully following the instructions
in this document.
Failure to do so may result in electrical shock, fire, or other hazards.
Electrical work must be performed by a qualified electrician. It must be performed in
accordance with technical standards related to electrical equipment, interior wiring
regulations, local codes, and the contents of these instructions. Be sure to use a
dedicated power supply circuit.
Insufficient power circuit capacity or improper electrical work may result in electrical
shock or fire.
Use only the designated cables for wiring, and connect them securely. Fasten cables so
that no external force is applied to the terminal connections.
Insufficient connections or cable fastening may result in heat generation, fire, or other
hazards.
CAUTION
Depending on the installation location, it may be necessary to install an earth leakage
breaker. Failure to do so may result in electrical shock or fire.
Do not install in kitchens, workshops, or other locations where there is oil mist in the air.
Do not install next to windows or in other locations exposed to direct sunlight or in direct
contact with outside air.
Do not install near an elevator, automatic door, industrial sewing machine, or other
devices that can be expected to produce electrical noise.
Accessories for Schedule Timer
*1 If the fuse blows as a result of a wiring short-circuit, miswiring, or overcurrent, replace it with a
125 V, 0.1 A fuse (Fig. 1).
*2 Use this connecting wire when using with weekly timer mode. Connect the provided
connecting wire (4 cores) to the power terminal (4P connector) of the schedule timer unit.
(Fig. 5)
Installing the Schedule Timer
<Note 1> Avoid twisting the inter-unit control wiring or the input/output wiring together with
power or other wiring, and avoid running them in the same metal conduit. Doing
so can cause malfunction.
<Note 2> Install the schedule timer at a location away from any sources of electrical noise.
<Note 3> Install a noise filter or take other appropriate action if electrical noise affects the
power supply circuit of the unit.
This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.
No. Supplied parts Q'ty
1
CN61 (T10) power wire
(with current fuse) *1
1
2
1.2m length of connecting
wire *2
1
3
Screws
M4 × 25
2
4
Spacers
2
5
Wire joints
6
6
Operation
manual
2
7
Installation
manual
1
No. Supplied parts Q'ty
Indoor unit control PCB CN61
(T10) connector (6P orange)
1. Power wire
Fuse
Fig. 1
(1) Open the panel on the schedule timer unit. Insert a standard (flathead) screwdriver or
similar tool into the notches on the bottom of the schedule timer unit to open and
remove the back case.
(2) Use the 2 supplied M4 small screws and install the schedule timer back case onto the
switch box. Before installing, use a screwdriver or similar tool to press on and open the
screw holes that correspond to the JIS box that is used.
When fastening the case, use spacers and do not tighten the screws too much. If the
schedule timer does not fit tightly against the wall, cut the spacers as required to make
adjustments.
(3) Connect the supplied power wire (2-core) and inter-unit control wire (3-core) to the
schedule timer unit.
(“Wiring for Weekly Timer mode”)
(4) Align the schedule timer unit with the tabs on the back case and press to install it.
Installation of connected schedule timers
When installing schedule timers (remote controller switches, system controllers, etc.)
onto the wall, use the method shown in Figs. 3 and 4.
* For maintenance reasons, leave a gap of 25 mm or more between the remote controller switch
and schedule timer if they are arranged in parallel above/below each other.
This remote controller has two methods of usage with the weekly timer and the
schedule timer.
The wiring method and switch setting are different in each case.
Wiring for Weekly Timer mode
Wiring Diagram (Be sure to use the provided wires for the connection wiring.)
Location The schedule timer and wired remote controller can be located on
either the right and left.
System Diagram
Switch box for 1 switch (no cover)
or switch box for 2 switches (no cover)
Spacer
Schedule
timer unit
M4 x 25 small
flat-head screws (2)
Decorative
cover (panel)
Under-case
(back case)
Fig. 2
Remote controller
wiring outlet
More than 125 mm
(From wall) (For connected
installation)
Switch box for 1
switch (no cover)
Fig. 3
More than
95 mm
Remote controller
wiring outlet
More than
125 mm
(From wall)
(For connected
installation)
Switch box for 2 switches
(no cover)
Fig. 4
More than
95 mm
Connecting wire
(accessory)
Clamp filter
Timer terminalPower terminal
Schedule
timer
Wired
remote
controller
Fig. 5
: Connector
4 wires
DC12V
: Terminal board
Schedule
timer
Wired
remote
controller
Indoor
unit
Outdoor
unit
Fig. 6
Wiring for the Schedule Timer mode
<Basic Wiring Diagram>
*1 In the case the schedule timer is connected to the 64 system central remote controller or
ON-OFF controller
*2 In the case the schedule timer is connected to the indoor unit for S-MMS
*3 In the case the schedule timer is connected to the TCC-LINK adapter
P1, L1, L2, L3 and L4 have no polarity.
Wiring
The schedule timer wiring can be connected by the following two methods. Select one of
these connection methods according to the actual installation location. When wiring,
extend the lengths of the wires using wire joints (accessory) and extension wires (field
supply).
Wiring procedures Connect the provided connecting wire to the power terminal (4P
connector) of the schedule timer.
The terminal attached to the clamp filter must be connected to the
schedule timer.
The power wiring and communication wiring has no polarity.
Wiring Max. Length Electric cable
specifications
P1: Power wire for schedule timer 100m 0.5mm
2
L1: Central control system wiring
L2,L3,L4: Indoor/Outdoor communication
line
L1+L2+
L3+L4
Less than 1000m MVVS 1.25mm
2
Less than 2000m MVVS 2.0 mm
2
<Note> This schedule timer is device connected to TCC-LINK.
The maximum number of schedule timer units that can be connected is 8. (A
maximum of 10 schedule timer units and other central control devices can be
connected.)
In the case of SDI/DI, an extra TCC-LINK adapter may be required.
<Note> When installing multiple schedule timers, avoid the use of
communication line.
Connection diagram (Be sure to use the provided wires as the power
wiring.)
Wiring specifications (1)
If a 64 system central remote controller (or ON-OFF controller) is installed (power is
supplied from the 64 system central remote controller):
U1
U2
U3
U4
U1
U2
P1
U3
U4
U1
U2
U3
U4
U1
U2
U3
U4
U1
P1
L1
L3
L2 L4
P1
U2
U1
U2
To power terminal
To communication
terminal
To power terminal
To communication
terminal
To power terminal
To communication
terminal
64 system central remote controller or
ON-OFF controller
Indoor unit
(Header unit)
Outdoor unit
(Header unit)
Outdoor unit
TCC-LINK
adapter
Indoor
unit
Wiring
specifications (1)
Wiring specifications (2)Wiring specifications (2)
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Schedule
timer *2
Schedule
timer *3
Indoor
unit
Indoor
unit
Indoor
unit
Refrigerant system 3
(S-MMS)
Refrigerant system 2
(SDI/DI)
Refrigerant system 1
(S-MMS)
Schedule timer *1
Fig. 7
U1
U2
Wire joint
(Not used)
BlueBlue Pink
Power terminal
(4P connector)
Communication
terminal (3P connector)
Schedule timer
Connecting wire (accessory)
Clamp filter
Field supply
64 system central remote controller
(Back side)
Communication
wiring
(blue + pink)
Inter-unit control wiring
Fig. 8
The power wiring and communication wiring has no polarity.
The length of the power wiring must be no more than 100 m.
The ground method of a shield wire (when using with the Schedule
Timer)
*1 In the case the schedule timer is connected to the 64 system central remote controller or
ON-OFF controller
*2 In the case the schedule timer is connected to the indoor unit for S-MMS
*3 In the case the schedule timer is connected to the TCC-LINK adapter
<Grounding of the shield wires>
The shield wires of the central control wiring should be connected at closed end, and
these should be single-point ground.
The terminal end (*4) of the shield wires should be open and insulated.
Explanation to Customers
After work is completed, present the Operation Manual and Information for the Person in
Charge of Installation (Electrical) Work to the customer.
Explain to the customer the methods for use of the system, as described in the
Operation Manual.
Memory Backup Switch
After installation is completed, check that the backup switch on the reverse side of the
schedule timer PCB is turned to ON.
(The backup battery will retain the current time for up to 100 hours.)
Wiring specifications (2)
If a 64 system central remote controller (or ON-OFF controller) is not installed (power is
supplied from the indoor unit):
<Note>
(1) The only functions of the schedule timer are indoor unit ON/OFF and remote
controller enable/disable operations.
(2) It is required that during installation, a 64 system central remote controller or wired
remote controller be installed next to the schedule timer so that operation mode
and other information can be checked.
(3) If the 64 system central remote controller or other central control device is not
present, the schedule timer cannot be used in combination with a system that does
not utilize remote controllers including high wall (KRT series) systems.
U2
U4
U1
U3
CN61(T10)
1. Supplied parts
Indoor unit control PCB
Field supply
Wire joint
(Not used)
Indoor/Outdoor units communication line
(for S-MMS)
Central control system wiring
(for SDI/DI)
(for SDI/DI)
(for S-MMS)
BlueBlue Pink
Communication
wiring
(blue + pink)
Power wiring
(black + white)
Power terminal
(4P connector)
Communication
terminal (3P connector)
Schedule timer
Black White
Fig. 9
U1
U2
U3
U4
U1
U2
U1
U2
U3
U4
U1
U2
U1
U2
U3
U4
*4
*4
*4
*4
U1
U2
U3
U4
Refrigerant system 1
(S-MMS)
Shield wiring for
central control
system (single-
point earth)
Shield wiring for
central control
system (single-
point earth)
Power
terminal
Communication
terminal
Indoor/Outdoor
units
communication line
Indoor/Outdoor units
crcommunication line
Shield wiring for central control system
(single-point earth)
Power terminal
Central control
system wiring
Outdoor unit
(Header unit)
Indoor
unit
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Schedule
Timer *1
Schedule
Timer *2
Schedule
Timer *2
64 System central
remote controller
or
ON-OFF controller
TCC-LINK
adapter
Indoor
unit
Indoor
unit
Indoor
unit
Outdoor unit
(Header unit)
Refrigerant
system 2
(SDI/DI)
Outdoor
unit
Refrigerant system 3
(S-MMS)
Fig. 10
ON
OFF
Backup switch
Backup battery
Fi