Carrier 40QAC Product Data
Download Product data of Carrier 38HDR Air Conditioner, Heat Pump for Free or View it Online on All-Guides.com. This version of Carrier 38HDR Manual compatible with such list of devices, as: 38HDR, 38QRR, 40QAC, 40QAQ
Brand: Carrier
Category: Air Conditioner , Heat Pump
Type: Product data
Model: Carrier 38HDR , Carrier 38QRR , Carrier 40QAC , Carrier 40QAQ
Pages: 42
16
PERFORMANCE DATA
COOLING CAPACITIES
38HDR018 / 40QAC024*
Te m p ° F ( ° C )
Air Entering
Condenser (Edb)
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
320/0.02 400/0.03 500/0.03
Air Entering Evaporator --- Ewb ° F (° C)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
55
(12.8)
TCG 17.2 18.7 20.1 21.5 17.7 19.1 20.5 21.8 18.1 19.5 20.8 22.1
SHG 16.8 15.0 12.9 10.7 17.2 15.7 13.3 10.9 18.1 16.4 13.8 11.2
TC 17.0 18.5 19.9 21.3 17.4 18.8 20.2 21.6 17.8 19.3 20.6 21.9
kW 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.95 0.94 0.94
CMP 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.76 0.75 0.76 0.75 0.76
LDB 46.3 50.2 54.9 59.7 49.0 52.1 56.8 61.4 51.3 54.2 58.7 63.1
LWB 41.6 46.9 52.5 58.2 43.0 48.4 54.0 59.7 44.5 49.9 55.4 61.1
65
(18.3)
TCG 16.3 18.2 19.6 21.1 17.0 18.6 20.0 21.4 17.7 18.9 20.3 21.6
SHG 16.3 14.9 12.8 10.6 17.0 15.5 13.2 10.8 17.7 16.4 13.7 11.1
TC 16.1 17.9 19.4 20.8 16.8 18.3 19.7 21.1 17.4 18.7 20.1 21.4
kW 1.06 1.05 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06
CMP 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.88
LDB 47.2 50.5 55.1 59.8 49.4 52.3 56.8 61.5 51.9 54.2 58.7 63.2
LWB 42.5 47.4 52.9 58.6 43.6 48.8 54.3 60.0 44.8 50.3 55.8 61.4
75
(23.9)
TCG 15.6 17.4 19.0 20.5 16.4 17.8 19.4 20.8 17.1 18.2 19.7 21.1
SHG 14.9 14.6 12.6 10.4 16.4 15.3 13.1 10.7 17.1 16.2 13.7 11.0
TC 15.4 17.2 18.8 20.3 16.2 17.5 19.1 20.6 16.9 17.9 19.5 20.9
kW 1.17 1.19 1.19 1.19 1.18 1.18 1.19 1.19 1.18 1.19 1.19 1.19
CMP 0.99 1.00 1.00 1.00 0.99 1.00 1.00 1.01 1.00 1.00 1.00 1.01
LDB 50.3 51.1 55.4 60.1 50.4 52.7 57.0 61.7 52.8 54.4 58.7 63.3
LWB 43.3 48.1 53.4 59.0 44.1 49.4 54.8 60.3 45.3 50.8 56.1 61.7
85
(29.4)
TCG 14.8 16.5 18.2 19.8 15.6 16.9 18.6 20.1 16.4 17.2 18.9 20.5
SHG 14.8 13.9 12.2 10.2 15.6 14.8 12.9 10.5 16.4 15.8 13.6 10.9
TC 14.5 16.2 18.0 19.6 15.4 16.6 18.3 19.9 16.1 17.0 18.6 20.2
kW 1.30 1.32 1.33 1.33 1.31 1.32 1.33 1.33 1.32 1.33 1.33 1.34
CMP 1.12 1.13 1.15 1.15 1.13 1.14 1.15 1.15 1.14 1.14 1.15 1.15
LDB 50.4 52.4 56.1 60.5 52.0 53.6 57.4 62.0 53.9 55.0 59.0 63.5
LWB 44.1 49.0 54.1 59.5 44.9 50.2 55.3 60.7 45.8 51.4 56.6 62.0
95
(35)
TCG 14.2 15.4 17.2 19.0 14.7 15.7 17.6 19.3 15.5 16.1 18.3 19.6
SHG 14.2 13.3 11.8 9.8 14.7 14.2 12.5 10.2 15.5 15.2 13.5 10.7
TC 13.9 15.2 17.0 18.7 14.5 15.5 17.3 19.0 15.2 15.9 18.0 19.3
kW 1.53 1.54 1.56 1.57 1.53 1.54 1.57 1.57 1.54 1.55 1.57 1.57
CMP 1.34 1.35 1.37 1.38 1.35 1.36 1.38 1.39 1.36 1.36 1.38 1.39
LDB 51.6 53.6 57.0 61.3 53.6 54.7 58.1 62.5 55.4 56.0 59.5 63.8
LWB 44.7 49.9 54.9 60.1 45.6 51.1 56.0 61.3 46.5 52.2 57.2 62.5
105
(40.6)
TCG 13.3 14.2 16.0 17.9 13.9 14.5 16.3 18.2 14.5 15.1 16.6 18.5
SHG 13.3 12.7 11.2 9.4 13.9 13.5 11.8 9.8 14.5 13.4 12.6 10.3
TC 13.1 13.9 15.7 17.6 13.6 14.2 16.0 17.9 14.3 14.9 16.4 18.2
kW 1.60 1.61 1.63 1.66 1.61 1.61 1.64 1.66 1.62 1.62 1.64 1.66
CMP 1.42 1.43 1.45 1.47 1.42 1.43 1.45 1.47 1.43 1.43 1.46 1.48
LDB 53.4 54.8 58.2 62.0 55.1 56.0 59.3 63.2 57.0 58.9 60.4 64.4
LWB 45.5 51.0 55.9 60.9 46.4 52.0 56.9 62.0 47.2 52.9 58.0 63.1
115
(46.1)
TCG 12.3 12.9 14.6 16.5 12.8 13.3 14.9 16.8 13.4 13.8 15.2 17.1
SHG 12.3 11.6 10.4 8.9 12.8 12.1 11.1 9.3 13.4 12.5 11.9 9.8
TC 12.1 12.7 14.4 16.3 12.6 13.1 14.7 16.6 13.2 13.5 14.9 16.9
kW 1.77 1.77 1.79 1.83 1.78 1.77 1.80 1.83 1.78 1.79 1.80 1.84
CMP 1.58 1.58 1.61 1.64 1.59 1.59 1.61 1.65 1.60 1.60 1.62 1.66
LDB 55.4 57.0 59.7 63.1 57.0 58.5 60.6 64.0 58.7 60.4 61.5 65.1
LWB 46.5 52.1 56.9 61.8 47.3 52.9 57.9 62.8 48.1 53.8 58.9 63.8
125
(51.7)
TCG 11.2 11.6 13.1 14.9 11.7 11.8 13.3 15.2 12.3 12.3 13.6 15.5
SHG 11.2 10.8 9.8 8.2 11.7 11.8 10.5 8.7 12.3 12.3 11.2 9.2
TC 11.0 11.3 12.9 14.7 11.5 11.5 13.1 14.9 12.0 12.0 13.3 15.2
kW 1.96 1.94 1.97 2.01 1.95 1.95 1.97 2.01 1.96 1.96 1.98 2.01
CMP 1.77 1.76 1.78 1.82 1.77 1.76 1.79 1.83 1.78 1.77 1.79 1.83
LDB 57.7 58.6 60.9 64.4 59.0 59.1 61.7 65.2 60.6 60.7 62.6 66.1
LWB 47.6 53.2 58.1 62.9 48.2 53.9 58.9 63.8 48.9 54.7 59.8 64.7
Rating Condition.
Not recommended for long--- term operation
BF --- B y p a s s Fa c t o r
CMP --- C o m p r e s so r
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- To t a l Po w e r
LDB --- L e a v i n g D r y Bu l b
LWB --- L e a v i n g We t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cooling Capacity (1000 Btuh)
TCG --- Gross C ooling Ca pacity (1000 Btuh)
* The 40QAC024 unit must be fi eld configured to an 018 size unit by changing the
motor speed fan tap plug. Refer to Installation Instructions for more details.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based o n 80_F (26.7_C) edb temperature o f air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
40QAC/38HDR -- 40QAQ/38QR
R