PERFORMANCE DATA (CONT.)
INSTANTANEOUS AND INTEG. HEATING RATINGS
40QAQ036 / 38QRR036
Air
Te m p e r a t ur e
Entering
Indoor Unit
°F(°C)
Indoor
Airflow
(CFM)
L --- M --- H
Item
Air Temperature Entering Outdoor Coil ° F (° C)
17 ( --- 8.3) 27 ( --- 2.8) 37 (2.8) 47 (8.3) 57 (13.9)
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
55
(12.8)
630
Cap 19.18 17.48 23.81 21.15 27.49 25.02 32.28 32.28 36.27 36.27
kW 2.29 2.38 2.48 2.58 2.77
750
Cap 19.56 17.83 24.21 21.50 28.14 25.60 32.89 32.89 36.97 36.97
kW 2.20 2.27 2.35 2.42 2.56
870
Cap 19.82 18.07 24.46 21.73 20.80 18.93 33.31 33.31 37.61 37.61
kW 2.13 2.19 2.24 2.29 2.41
60
(15.6)
400
Cap 18.73 17.08 23.41 20.79 19.96 18.17 31.71 31.71 35.66 35.66
kW 2.39 2.51 2.63 2.75 2.90
480
Cap 19.15 17.46 23.84 21.17 19.43 17.68 23.22 23.22 36.48 36.48
kW 2.29 2.25 2.21 2.16 2.69
550
Cap 19.44 17.72 24.13 21.43 18.84 17.15 19.34 19.34 37.10 37.10
kW 2.23 2.15 2.06 1.98 2.53
65
(18.3)
400
Cap 18.25 16.64 22.98 20.41 26.73 24.33 31.26 31.26 35.17 35.17
kW 2.49 2.61 2.73 2.85 3.03
480
Cap 18.68 17.03 23.43 20.81 27.17 24.72 32.05 32.05 35.98 35.98
kW 2.40 2.48 2.55 2.63 2.82
550
Cap 18.99 17.32 23.75 21.09 27.55 25.07 32.48 32.48 36.59 36.59
kW 2.33 2.40 2.47 2.54 2.66
70
(21.1)
400
Cap 17.73 16.16 22.50 19.98 26.34 23.97 30.75 30.75 34.49 34.49
kW 2.59 2.71 2.83 2.95 3.27
480
Cap 18.18 16.58 23.00 20.43 26.82 24.40 31.59 31.59 35.53 35.53
kW 2.51 2.58 2.66 2.74 3.00
550
Cap 18.51 16.87 23.33 20.72 27.12 24.68 32.00 32.00 36.09 36.09
kW 2.44 2.51 2.59 2.67 2.79
75
(23.9)
400
Cap 17.18 8.66 21.95 19.50 25.88 8.66 30.25 30.25 33.76 33.76
kW 2.70 2.82 2.95 3.07 3.45
480
Cap 17.64 8.89 22.51 19.99 26.39 8.89 31.09 31.09 34.98 34.98
kW 2.61 2.70 2.78 2.87 3.08
550
Cap 17.98 16.40 22.89 20.33 26.73 24.32 31.60 31.60 35.57 35.57
kW 2.54 2.61 2.67 2.74 2.93
80
(26.7)
400
Cap 16.60 15.13 21.38 18.99 25.41 23.12 29.68 29.68 33.34 33.34
kW 2.80 2.93 3.06 3.19 3.55
480
Cap 17.07 15.57 21.95 19.49 25.94 23.60 30.37 30.37 34.42 34.42
kW 2.72 2.83 2.93 3.04 3.31
550
Cap 17.42 8.66 22.37 19.86 26.32 23.95 31.09 31.09 35.07 35.07
kW 2.65 2.73 2.80 2.87 3.11
Rating Condition.
Not recommended for long--- term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
40QAC/38HDR -- 40QAQ/38QR
R