32
PERFORMANCE DATA (CONT.)
INSTANTANEOUS AND INTEG. HEATING RATINGS
40QAQ048 / 38QRR048
Air
Te m p e r a t ur e
Entering
Indoor Unit
°F(°C)
Indoor
Airflow
(CFM)
L --- M --- H
Item
Air Temperature Entering Outdoor Coil ° F (° C)
17 ( --- 8.3) 27 ( --- 2.8) 37 (2.8) 47 (8.3) 57 (13.9)
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
55
(12.8)
820
Cap 27.65 25.21 33.34 29.61 38.58 35.11 45.46 45.46 50.81 50.81
kW 3.24 3.44 3.64 3.84 4.14
975
Cap 28.09 25.61 33.91 30.12 39.36 35.81 46.08 46.08 51.85 51.85
kW 3.12 3.28 3.44 3.60 3.86
1130
Cap 28.52 26.01 34.32 30.48 39.76 36.19 46.61 46.61 52.82 52.82
kW 3.03 3.17 3.30 3.43 3.66
60
(15.6)
820
Cap 27.09 24.70 32.79 29.12 38.22 34.78 44.77 44.77 50.24 50.24
kW 3.39 3.59 3.80 4.00 4.32
975
Cap 27.62 25.18 33.40 29.67 38.90 35.40 45.56 45.56 51.24 51.24
kW 3.27 3.44 3.60 3.77 4.04
1130
Cap 27.99 25.52 33.80 30.02 39.32 35.78 46.08 46.08 51.94 51.94
kW 3.17 3.32 3.46 3.60 3.83
65
(18.3)
820
Cap 26.49 24.15 32.21 28.60 37.67 34.28 44.22 44.22 49.61 49.61
kW 3.53 3.74 3.96 4.17 4.50
975
Cap 27.03 24.64 32.83 29.16 38.37 34.92 45.02 45.02 50.60 50.60
kW 3.41 3.59 3.77 3.95 4.22
1130
Cap 27.41 24.99 33.26 29.54 38.83 35.33 45.55 45.55 51.32 51.32
kW 3.32 3.47 3.62 3.77 4.01
70
(21.1)
820
Cap 25.86 23.58 31.59 28.05 37.08 33.74 43.67 43.67 48.91 48.91
kW 3.67 3.89 4.12 4.35 4.68
975
Cap 26.42 24.09 32.23 28.63 37.80 34.40 44.50 44.50 49.98 49.98
kW 3.55 3.74 3.94 4.13 4.41
1130
Cap 26.80 24.43 32.67 29.02 38.28 34.84 45.01 45.01 50.68 50.68
kW 3.46 3.63 3.79 3.95 4.20
75
(23.9)
820
Cap 25.21 8.66 30.94 27.48 36.46 8.66 43.29 43.29 48.29 48.29
kW 3.81 4.05 4.30 4.54 4.87
975
Cap 25.77 8.89 31.59 28.06 37.20 8.89 44.18 44.18 49.33 49.33
kW 3.70 3.90 4.11 4.32 4.60
1130
Cap 26.16 23.85 32.05 28.47 37.70 34.31 44.53 44.53 50.03 50.03
kW 3.61 3.79 3.96 4.14 4.40
80
(26.7)
820
Cap 24.50 22.34 30.26 26.87 35.81 32.59 42.95 42.95 47.61 47.61
kW 3.95 4.21 4.47 4.73 5.06
975
Cap 25.08 22.86 30.92 27.46 36.56 33.27 43.74 43.74 48.63 48.63
kW 3.84 4.06 4.29 4.51 4.80
1130
Cap 25.46 8.66 31.39 27.88 37.08 33.74 44.22 44.22 49.36 49.36
kW 3.76 3.95 4.14 4.33 4.59
Rating Condition.
Not recommended for long--- term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
40QAC/38HDR -- 40QAQ/38QR
R