Carrier 40QAC Product Data
Download Product data of Carrier 38HDR Air Conditioner, Heat Pump for Free or View it Online on All-Guides.com. This version of Carrier 38HDR Manual compatible with such list of devices, as: 38HDR, 38QRR, 40QAC, 40QAQ
Brand: Carrier
Category: Air Conditioner , Heat Pump
Type: Product data
Model: Carrier 38HDR , Carrier 38QRR , Carrier 40QAC , Carrier 40QAQ
Pages: 42
33
PERFORMANCE DATA (CONT.)
INSTANTANEOUS AND INTEG. HEATING RATINGS
40QAQ060 / 38QRR060
Air
Te m p e r a t ur e
Entering
Indoor Unit
°F(°C)
Indoor
Airflow
(CFM)
L --- M --- H
Item
Air Temperature Entering Outdoor Coil ° F (° C)
17 ( --- 8.3) 27 ( --- 2.8) 37 (2.8) 47 (8.3) 57 (13.9)
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
55
(12.8)
1040
Cap 31.97 29.15 38.41 34.12 42.34 38.53 53.78 53.78 57.10 57.10
kW 3.73 3.87 4.02 4.16 4.26
1220
Cap 32.33 29.48 39.03 34.67 42.99 39.12 54.83 54.83 58.41 58.41
kW 3.62 3.76 3.89 4.03 4.14
1600
Cap 32.89 29.99 39.62 35.18 43.44 39.53 55.52 55.52 59.30 59.30
kW 3.44 3.55 3.65 3.76 3.84
60
(15.6)
1040
Cap 31.21 28.46 37.64 33.43 41.36 37.64 52.67 52.67 55.60 55.60
kW 3.85 4.00 4.15 4.31 4.40
1220
Cap 31.81 29.00 38.50 34.20 42.51 38.68 54.28 54.28 57.69 57.69
kW 3.76 3.91 4.06 4.21 4.31
1600
Cap 32.37 29.52 39.16 34.78 43.10 39.23 55.05 55.05 58.69 58.69
kW 3.59 3.70 3.82 3.94 4.02
65
(18.3)
1040
Cap 30.58 27.88 36.98 32.85 40.71 37.04 51.95 51.95 55.16 55.16
kW 4.01 4.17 4.33 4.48 4.60
1220
Cap 31.26 28.50 37.93 33.69 41.93 38.16 53.82 53.82 57.17 57.17
kW 3.90 4.06 4.22 4.38 4.49
1600
Cap 31.81 29.01 38.60 34.28 42.72 38.88 54.54 54.54 58.11 58.11
kW 3.73 3.86 3.98 4.11 4.20
70
(21.1)
1040
Cap 30.11 27.46 36.27 32.21 39.96 36.36 51.01 51.01 54.24 54.24
kW 4.19 4.35 4.50 4.65 4.77
1220
Cap 30.64 27.94 37.29 33.12 41.26 37.54 53.08 53.08 56.57 56.57
kW 4.05 4.22 4.39 4.55 4.68
1600
Cap 31.22 28.46 37.97 33.72 42.06 38.27 54.03 54.03 57.51 57.51
kW 3.88 4.02 4.16 4.30 4.39
75
(23.9)
1040
Cap 29.34 8.66 35.76 31.76 39.08 8.66 49.96 49.96 53.15 53.15
kW 4.36 4.51 4.67 4.83 4.95
1220
Cap 29.93 8.89 36.60 32.51 40.51 8.89 52.18 52.18 55.80 55.80
kW 4.20 4.38 4.55 4.72 4.86
1600
Cap 30.55 27.85 37.27 33.10 41.35 37.63 53.38 53.38 56.87 56.87
kW 4.01 4.17 4.32 4.48 4.58
80
(26.7)
1040
Cap 28.69 26.16 35.12 31.19 38.17 34.74 48.75 48.75 51.91 51.91
kW 4.54 4.69 4.85 5.00 5.12
1220
Cap 29.22 26.64 35.82 31.82 39.52 35.97 51.08 51.08 54.65 54.65
kW 4.38 4.55 4.71 4.88 5.02
1600
Cap 29.82 8.66 36.52 32.44 40.52 36.87 52.37 52.37 56.17 56.17
kW 4.16 4.32 4.49 4.65 4.77
Rating Condition.
Not recommended for long--- term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
40QAC/38HDR -- 40QAQ/38QR
R