7
AHRI* CAPACITY RATINGS
System
Ty p e
Outdoor Section Indoor Section
Standard CFM
Net Cool-
ing BTUH
SEER EER
High Heat
Outdoor Indoor BTUH HSPF
Cooling
3 8 H D R 0 1 8 --- --- --- 3 4 0 QA C 0 2 4 --- --- --- 3 1720 480 18,000 13 11.5 N/A N/A
3 8 H D R 0 2 4 --- --- --- 3 4 0 QA C 0 2 4 --- --- --- 3 1720 550 23,000 13 11.5 N/A N/A
3 8 H D R 0 3 0 --- --- --- 3 4 0 QA C 0 3 6 --- --- --- 3 3900 840 29,000 13 12.0 N/A N/A
3 8 H D R 0 3 6 --- --- --- 3 4 0 QA C 0 3 6 --- --- --- 3 3900 840 33,000 13 11.4 N/A N/A
3 8 H D R 0 3 6 --- --- --- 5 4 0 QA C 0 3 6 --- --- --- 3 3900 840 33,000 13 11.4 N/A N/A
3 8 H D R 0 3 6 --- --- --- 6 4 0 QA C 0 3 6 --- --- --- 3 3900 840 33,000 13 11.4 N/A N/A
3 8 H D R 0 4 8 --- --- --- 3 4 0 QA C 0 4 8 --- --- --- 3 3900 1130 46,000 13 11.5 N/A N/A
3 8 H D R 0 4 8 --- --- --- 5 4 0 QA C 0 4 8 --- --- --- 3 3900 1130 46,000 13 11.5 N/A N/A
3 8 H D R 0 4 8 --- --- --- 6 4 0 QA C 0 4 8 --- --- --- 3 3900 1130 46,000 13 11.5 N/A N/A
3 8 H D R 0 6 0 --- --- --- 3 4 0 QA C 0 6 0 --- --- --- 3 3900 1600 57,000 13 11.4 N/A N/A
3 8 H D R 0 6 0 --- --- --- 5 4 0 QA C 0 6 0 --- --- --- 3 3900 1600 57,000 13 11.4 N/A N/A
3 8 H D R 0 6 0 --- --- --- 6 4 0 QA C 0 6 0 --- --- --- 3 3900 1600 57,000 13 11.4 N/A N/A
Heat PumpsHeat Pumps
3 8 QR R 0 1 8 --- --- --- 3 4 0 QA Q0 2 4 --- --- --- 3 1720 480 17,000 13 11.7 17,000 7.7
3 8 QR R 0 2 4 --- --- --- 3 4 0 QA Q0 2 4 --- --- --- 3 1720 550 23,000 13 11.4 23,800 7.7
3 8 QR R 0 3 0 --- --- --- 3 4 0 QA Q0 3 6 --- --- --- 3 3900 840 28,000 13 11.2 28,800 7.7
3 8 QR R 0 3 6 --- --- --- 3 4 0 QA Q0 3 6 --- --- --- 3 3900 840 33,000 13 11.6 32,000 7.7
3 8 QR R 0 3 6 --- --- --- 5 4 0 QA Q0 3 6 --- --- --- 3 3900 840 33,000 13 11.6 32,000 7.7
3 8 QR R 0 3 6 --- --- --- 6 4 0 QA Q0 3 6 --- --- --- 3 3900 840 33,000 13 11.6 32,000 7.7
3 8 QR R 0 4 8 --- --- --- 3 4 0 QA Q0 4 8 --- --- --- 3 3900 1130 45000 13 11.5 45000 7.7
3 8 QR R 0 4 8 --- --- --- 5 4 0 QA Q0 4 8 --- --- --- 3 3900 1130 45000 13 11.5 45000 7.7
3 8 QR R 0 4 8 --- --- --- 6 4 0 QA Q0 4 8 --- --- --- 3 3900 1130 45000 13 11.5 45000 7.7
3 8 QR R 0 6 0 --- --- --- 3 4 0 QA Q0 6 0 --- --- --- 3 3900 1600 56000 13 11.4 56000 7.7
3 8 QR R 0 6 0 --- --- --- 5 4 0 QA Q0 6 0 --- --- --- 3 3900 1600 56000 13 11.4 56000 7.7
3 8 QR R 0 6 0 --- --- --- 6 4 0 QA Q0 6 0 --- --- --- 3 3900 1600 56000 13 11.4 56000 7.7
*Air Conditioning, Heating & Refrigeration Institute
Legend
HSPF --- Heating Seasonal Performance Factor
EER --- Energy Efficiency Rating
SEER --- Seasonal Energy E fficiency Ratio
NOTES:
1. Ratings are net values reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80_F ( 26.67_ C) db, 67_F (19.44_C) wb air
entering indoor unit and 95_F(35_C) db air entering outdoor unit. High Temperature Heating Standard: 70_F (21.11_C) db air entering indoor unit and 47_F
(8.33_C) db, 43_F (6.11_C) wb air entering outdoor unit.
2. Ratings are based on 25 ft. (7.62 m) of interconnecting refrigerant lines.
3. All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data tables f or airflows at all available fan speeds.
CLEARANCES -- OUTDOOR UNIT
A
D
B
Air-inlet
Air-outlet
C
E
A08436
UNIT Coil Facing Wall --- in. (mm)
Fan F acing Wall --- in. (mm)
A 24 (610)
24 (610)
B 36 (914)
36 (914)
C 36 (914)
8 (203)
D 6 (152)
8 (203)
E 6 (152)
8 (203)
Fig. 4 – Outdoor Unit Clearance
40QAC/38HDR -- 40QAQ/38QR
R