Split Type Installation Manual
20
11.4 Electric Connection to the Outdoor Unit
Warning
!
Danger of breakdowns or malfunction. If the fuse
on the PC board is blown please change it
with type T. 25A/250V.
• Remove the protective covering in front of the
electrical connections in the outdoor unit.
• Loosen the screws in the terminal and fully insert the
cable , ensuring the cable sheath extends to the
terminal leaving no exposed conductorr before
tightening the screws to clamp the cable. Connect the
wires to their respective terminal, ensuring all
connections are tight.
Warning
!
Danger of malfunction and breakdowns resulting
from water penetration.
Always terminate the interconnecting cable from
below the cable entry to avoid water penetration
into the terminal box
Warning
!
Danger of malfunction and breakdowns resulting
from short-circuits.
If using a cable with additional cores, insulate
the unused cable wires using electrical tape and
ensure that they cannot come into contact with
any other parts of the electrical installation.
• Check the cable retainer is sufficiently tight to avoid
undue strain on the connections.
• Check that the cables are correctly secured and
connected.
• Replace the protective wiring cover.
11 Electric Wiring
11.5 Electrical Characteristics
V 12-025 W
V 12-035 W
V 12-050 W
V 12-060 W
Power supply (V/Ph/Hz)
230/1/50
230/1/50
230/1/50
230/1/50
Supply
Recommended minimum supply section up to 25 meters (mm
2
)
1,5
1,5
2,5
2,5
Indoor / Outdoor
Indoor
Indoor
Indoor
Indoor
Thermal-magnetic circuit breaker, type D (A)
10
10
16
16
Recommended minimum interconnection section up to 25 meters (mm
2
)
1,5
1,5
2,5
2,5
Inteconnect shielded cable or not (YES / NO)
NO
NO
NO
NO
Residual current protector (A)
0,03
0,03
0,03
0,03
Table 11.1 Electrical Characteristics.
V 12-060 M2W
Power supply (V/Ph/Hz)
230/1/50
Supply 1
Recommended minimum supply section up to 25 meters (mm
2
)
2,5
Indoor / Outdoor
Outdoor
Thermal-magnetic circuit breaker, type D (A)
16
Supply 1
Recommended minimum supply section up to 25 meters (mm
2
)
1,5
Indoor / Outdoor
Indoor
Thermal-magnetic circuit breaker, type D (A)
10
Recommended minimum interconnection section up to 25 meters (mm
2
)
1,5
Inteconnect shielded cable or not (YES / NO)
NO
Residual current protector (A)
0,03