Vaillant V 12-060 M2W Installation Manual

Download Installation manual of Vaillant V 12-025 W Air Conditioner for Free or View it Online on All-Guides.com. This version of Vaillant V 12-025 W Manual compatible with such list of devices, as: V 12-025 W, V 12-060 M2W, V 12-035 W, V 12-050 W, V 12-060 W

Vaillant V 12-025 W Installation manual - Page 1
1
Vaillant V 12-025 W Installation manual - Page 2
2
Vaillant V 12-025 W Installation manual - Page 3
3
Vaillant V 12-025 W Installation manual - Page 4
4
Vaillant V 12-025 W Installation manual - Page 5
5
Vaillant V 12-025 W Installation manual - Page 6
6
Vaillant V 12-025 W Installation manual - Page 7
7
Vaillant V 12-025 W Installation manual - Page 8
8
Vaillant V 12-025 W Installation manual - Page 9
9
Vaillant V 12-025 W Installation manual - Page 10
10
Vaillant V 12-025 W Installation manual - Page 11
11
Vaillant V 12-025 W Installation manual - Page 12
12
Vaillant V 12-025 W Installation manual - Page 13
13
Vaillant V 12-025 W Installation manual - Page 14
14
Vaillant V 12-025 W Installation manual - Page 15
15
Vaillant V 12-025 W Installation manual - Page 16
16
Vaillant V 12-025 W Installation manual - Page 17
17
Vaillant V 12-025 W Installation manual - Page 18
18
Vaillant V 12-025 W Installation manual - Page 19
19
Vaillant V 12-025 W Installation manual - Page 20
20
Vaillant V 12-025 W Installation manual - Page 21
21
Vaillant V 12-025 W Installation manual - Page 22
22
Vaillant V 12-025 W Installation manual - Page 23
23
Vaillant V 12-025 W Installation manual - Page 24
24
Vaillant V 12-025 W Installation manual - Page 25
25
Vaillant V 12-025 W Installation manual - Page 26
26
Vaillant V 12-025 W Installation manual - Page 27
27
Vaillant V 12-025 W Installation manual - Page 28
28
Split Type Installation Manual
20
11.4 Electric Connection to the Outdoor Unit
Warning
!
Danger of breakdowns or malfunction. If the fuse
on the PC board is blown please change it
with type T. 25A/250V.
• Remove the protective covering in front of the
electrical connections in the outdoor unit.
• Loosen the screws in the terminal and fully insert the
cable , ensuring the cable sheath extends to the
terminal leaving no exposed conductorr before
tightening the screws to clamp the cable. Connect the
wires to their respective terminal, ensuring all
connections are tight.
Warning
!
Danger of malfunction and breakdowns resulting
from water penetration.
Always terminate the interconnecting cable from
below the cable entry to avoid water penetration
into the terminal box
Warning
!
Danger of malfunction and breakdowns resulting
from short-circuits.
If using a cable with additional cores, insulate
the unused cable wires using electrical tape and
ensure that they cannot come into contact with
any other parts of the electrical installation.
• Check the cable retainer is sufficiently tight to avoid
undue strain on the connections.
• Check that the cables are correctly secured and
connected.
• Replace the protective wiring cover.
11.5 Electrical Characteristics
V 12-025 W
V 12-035 W
V 12-050 W
V 12-060 W
Power supply (V/Ph/Hz)
230/1/50
230/1/50
230/1/50
230/1/50
Supply
Recommended minimum supply section up to 25 meters (mm
2
)
1,5
1,5
2,5
2,5
Indoor / Outdoor
Indoor
Indoor
Indoor
Indoor
Thermal-magnetic circuit breaker, type D (A)
10
10
16
16
Recommended minimum interconnection section up to 25 meters (mm
2
)
1,5
1,5
2,5
2,5
Inteconnect shielded cable or not (YES / NO)
NO
NO
NO
NO
Residual current protector (A)
0,03
0,03
0,03
0,03
Table 11.1 Electrical Characteristics.
V 12-060 M2W
Power supply (V/Ph/Hz)
230/1/50
Supply 1
Recommended minimum supply section up to 25 meters (mm
2
)
2,5
Indoor / Outdoor
Outdoor
Thermal-magnetic circuit breaker, type D (A)
16
Supply 1
Recommended minimum supply section up to 25 meters (mm
2
)
1,5
Indoor / Outdoor
Indoor
Thermal-magnetic circuit breaker, type D (A)
10
Recommended minimum interconnection section up to 25 meters (mm
2
)
1,5
Inteconnect shielded cable or not (YES / NO)
NO
Residual current protector (A)
0,03