Vaillant V 12-060 M2W Installation Manual

Download Installation manual of Vaillant V 12-025 W Air Conditioner for Free or View it Online on All-Guides.com. This version of Vaillant V 12-025 W Manual compatible with such list of devices, as: V 12-025 W, V 12-060 M2W, V 12-035 W, V 12-050 W, V 12-060 W

Vaillant V 12-025 W Installation manual - Page 1
1
Vaillant V 12-025 W Installation manual - Page 2
2
Vaillant V 12-025 W Installation manual - Page 3
3
Vaillant V 12-025 W Installation manual - Page 4
4
Vaillant V 12-025 W Installation manual - Page 5
5
Vaillant V 12-025 W Installation manual - Page 6
6
Vaillant V 12-025 W Installation manual - Page 7
7
Vaillant V 12-025 W Installation manual - Page 8
8
Vaillant V 12-025 W Installation manual - Page 9
9
Vaillant V 12-025 W Installation manual - Page 10
10
Vaillant V 12-025 W Installation manual - Page 11
11
Vaillant V 12-025 W Installation manual - Page 12
12
Vaillant V 12-025 W Installation manual - Page 13
13
Vaillant V 12-025 W Installation manual - Page 14
14
Vaillant V 12-025 W Installation manual - Page 15
15
Vaillant V 12-025 W Installation manual - Page 16
16
Vaillant V 12-025 W Installation manual - Page 17
17
Vaillant V 12-025 W Installation manual - Page 18
18
Vaillant V 12-025 W Installation manual - Page 19
19
Vaillant V 12-025 W Installation manual - Page 20
20
Vaillant V 12-025 W Installation manual - Page 21
21
Vaillant V 12-025 W Installation manual - Page 22
22
Vaillant V 12-025 W Installation manual - Page 23
23
Vaillant V 12-025 W Installation manual - Page 24
24
Vaillant V 12-025 W Installation manual - Page 25
25
Vaillant V 12-025 W Installation manual - Page 26
26
Vaillant V 12-025 W Installation manual - Page 27
27
Vaillant V 12-025 W Installation manual - Page 28
28
Split Type Installation Manual
21
12 Preparation for Use
This consists of the following steps:
• Checking for Leaks.
• Evacuation of the installation.
• Start up.
• Troubleshooting.
12.1 Checking for leaks
Fig. 12.1 Checking for leaks in the installation.
Legend
1 Suction valve (gas)
2 Return valve (liquid)
3 Service manifold (suitable for R410a refrigerant)
4 Non-return valve
5 Gauge lines
6 Nitrogen cylinder
Warning
!
Use of high pressure gas - risk of injury. Pressure
testing should only be undertaken by competent
and qualified persons.
• Connect a service manifold set to the service port on
the gas line stop valve of the outdoor unit.
• Connect a nitrogen cylinder to the charging hose of
the refrigerant gauges.
• Carefully open the valves on the service manifold to
allow the nitrogen to enter the installation.
Caution do not open the service valve on the outdoor
unit as this will release the pre-charged refrigerant
from the outdoor unit.
• In the event of using R-410A coolant set it to 40 bar(g)
of pressure, for 10/20 min.
• Check that all the connections and joints are gastight.
If any leaks are found, repair and start the process
again from the beginning.
• On satisfactory completion of the test, close all the
valves on the service manifold and remove the
nitrogen cylinder.
• Release the pressure from the system by slowly
opening the valves on the service manifold.
• Do not continue to the next step until the pressure
test has been successfully completed.