Bunn LCA-2 LCC-2 Installation And Operating Manual

Download Installation and operating manual of Bunn LCA-2 LCC-2 Coffee Maker for Free or View it Online on All-Guides.com.

Brand: Bunn

Category: Coffee Maker

Type: Installation and operating manual for Bunn LCA-2 LCC-2

Pages: 28 (0.73 Mb)

Download Bunn LCA-2 LCC-2 Installation and operating manual

Bunn LCA-2 LCC-2 Installation and operating manual - Page 1
1
Bunn LCA-2 LCC-2 Installation and operating manual - Page 2
2
Bunn LCA-2 LCC-2 Installation and operating manual - Page 3
3
Bunn LCA-2 LCC-2 Installation and operating manual - Page 4
4
Bunn LCA-2 LCC-2 Installation and operating manual - Page 5
5
Bunn LCA-2 LCC-2 Installation and operating manual - Page 6
6
Bunn LCA-2 LCC-2 Installation and operating manual - Page 7
7
Bunn LCA-2 LCC-2 Installation and operating manual - Page 8
8
Bunn LCA-2 LCC-2 Installation and operating manual - Page 9
9
Bunn LCA-2 LCC-2 Installation and operating manual - Page 10
10
Bunn LCA-2 LCC-2 Installation and operating manual - Page 11
11
Bunn LCA-2 LCC-2 Installation and operating manual - Page 12
12
Bunn LCA-2 LCC-2 Installation and operating manual - Page 13
13
Bunn LCA-2 LCC-2 Installation and operating manual - Page 14
14
Bunn LCA-2 LCC-2 Installation and operating manual - Page 15
15
Bunn LCA-2 LCC-2 Installation and operating manual - Page 16
16
Bunn LCA-2 LCC-2 Installation and operating manual - Page 17
17
Bunn LCA-2 LCC-2 Installation and operating manual - Page 18
18
Bunn LCA-2 LCC-2 Installation and operating manual - Page 19
19
Bunn LCA-2 LCC-2 Installation and operating manual - Page 20
20
Bunn LCA-2 LCC-2 Installation and operating manual - Page 21
21
Bunn LCA-2 LCC-2 Installation and operating manual - Page 22
22
Bunn LCA-2 LCC-2 Installation and operating manual - Page 23
23
Bunn LCA-2 LCC-2 Installation and operating manual - Page 24
24
Bunn LCA-2 LCC-2 Installation and operating manual - Page 25
25
Bunn LCA-2 LCC-2 Installation and operating manual - Page 26
26
Bunn LCA-2 LCC-2 Installation and operating manual - Page 27
27
Bunn LCA-2 LCC-2 Installation and operating manual - Page 28
28
4
ELECTRICAL REQUIREMENTS
CAUTION: The dispenser must remain disconnected from the power source until specified in Electrical Hook-Up.
The LCA-2 and LCC-2 dispensers are supplied with a 120-volt / 15 Amp cord set and require a 2-wire, grounded,
individual branch circuit rated for 120 volts AC, 15 amp, single phase, 60Hz. The mating connector must be
a NEMA 5-15R.
The LCA-2C and LCC-2C dispensers are supplied with a 120-volt / 20 Amp cord set and require a 2-wire,
grounded, individual branch circuit rated for 120 volts AC, 20 amp, single phase, 60Hz. The mating connector
must be a NEMA 5-20R.
These dispensers can be Field Wired for 208 or 240 volt applications. This requires a 2 or 3-wire, grounded,
individual branch circuit rated for 208/240 volts AC, 30 amp, single phase, 60 Hz.
NOTE: The internal terminal block must be rewired for 208/240 applications, (see Optional Field Wiring Diagram).
120V A.C.
120V A.C.
208 or
240V A.C.
HEATER RED
208 or
240V A.C.
120V A.C.
10A. FUSE - WHITE
HEATER RED
10A. FUSE - WHITE
10A. FUSE - BLACK
LIMIT SW. - BLACK
HEATER RED
10A. FUSE - WHITE
10A. FUSE - BLACK
LIMIT SW. - BLACK
10A. FUSE - BLACK
LIMIT SW. - BLACK
FIELD WIRING TERMINAL BLOCK DIAGRAM
For all 208 - 240 Volt Connections: Use No. 10 AWG Wires suitable for 90°C (194 °F)
1. Unit shipped per Fig. 1, wired for 120V A.C./2-Wire.
2. For 208 - 240V A.C./2-Wire per Fig. 2: Move both the Red-Heater wire and the White-Fuse wire to the Top Red Terminal as shown.
3. For 120/208 - 240V A.C./3-Wire per Fig. 3: Move the Red Heater wire to the Top Red Terminal as shown.
Fig. 1 Fig. 2 Fig. 3
PLUMBING REQUIREMENTS
The dispenser may be connected to a cold or hot water system (140°F Max.) with operating pressure between 20
and 90 psi (138 and 620 kPa) from a 1/2" or larger supply line. A shut-off valve should be installed in the line before
the dispenser. Install a regulator in the line when pressure is greater than 90 psi (620 kPa) to reduce it to 50 psi
(345 kPa). The water inlet fitting is 3/8" flare. Dispensers set up to deliver to 1.8 Oz./sec. (53.2 ml/sec) per dispense
tip, require a water supply source that can deliver a minimum of 1.7 gpm (6.4 lpm) at the inlet fitting. Dispensers
set up to deliver 2.6 Oz./sec. (76.9 lpm) per dispense tip, require a water supply source that can deliver a minimum
of 2.4 gpm (9.2 lpm) at the inlet fitting.
NOTE: Bunn-O-Matic recommends 3/8" tubing from the 1/2" water supply line. At least 18 inches of FDA approved
flexible beverage tubing, such as reinforced braided polyethylene or silicone, before the dispenser will facilitate
movement to clean the counter top. It can be purchased direct from Bunn-O-Matic (part number 00326.0000).
Bunn-O-Matic does not recommend the use of a saddle valve to install the dispenser. The size and shape of the
hole made in the supply line by this type of device may restrict water flow.
This equipment must be installed to comply with the Basic Plumbing Code of the Building Officials
and Code Administrators International, Inc. (BOCA) and the Food Service Sanitation Manual of the
Food and Drug Administration (FDA).