Siemens LIM-1 Installation Instructions

Download Installation instructions of Siemens LIM-1 Power distribution unit for Free or View it Online on All-Guides.com.

Brand: Siemens

Category: Power distribution unit

Type: Installation instructions for Siemens LIM-1

Pages: 2

Download Siemens LIM-1 Installation instructions

Siemens LIM-1 Installation instructions - Page 1
1
Siemens LIM-1 Installation instructions - Page 2
2
P/N 315-049552-6
OPERATION
The Model LIM-1 Loop Isolator module from Siemens
Industry, Inc., isolates short circuits on MXL and
FireFinder-XLS intelligent device loops. By placing
devices between LIM-1s during installation, a short in
the wiring within that group is disconnected from the
rest of the loop. The remainder of the devices
continue to operate. The LIM-1 operates in both
Class A and Class B circuits.
A yellow LED flashes when a device detects a short
circuit. The LIM-1 then isolates that part of the loop.
When the short is removed, the LIM-1 automatically
restores the loop to normal operation. The LIM-1
does not have a loop address and therefore does not
require address programming nor does it reduce the
loop capacity below 60 (MXL) or 252 (XLS) devices.
ELECTRICAL RATINGS
Installation Instructions
MODEL LIM-1
Loop Isolator Module
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
INSTALLATION
Remove all system power before installation, first
the battery and then the AC.
Refer to Figure 1 for the location and number of the
screw terminals on the LIM-1. The LIM-1 has two
input terminals, two output terminals and an earth
ground as listed below:
Terminal Number Description
1 Loop + IN
2 Loop - IN
3 Loop + OUT
4 Loop - OUT
5 Earth Ground
MECHANICAL INSTALLATION (See Figure 2)
1. Use a standard 3
1
/2-inch deep, double gang
electrical switchbox or a 4-inch square electrical
box that is 2
1
/8 inches deep.
2. Connect the field wiring. Press the LIM-1 into the
box and fasten the module plate to the box.
3. Cover the module front plate with the plate
supplied and fasten with screws supplied.
Figure 2
Mounting the LIM-1
Figure 1
Model LIM-1
SWITCHPLATE
5-INCHES SQUARE
(SUPPLIED)
SWITCHPLATE
5-INCHES SQUARE
(SUPPLIED)
4-INCH SQUARE BOX
2 1/8-INCHES DEEP
DOUBLE GANG BOX
3 1/2-INCHES DEEP
tnerruCeludoMCDV5evitcAAm0
tnerruCeludoMCDV42evitcAAu067
tnerruCeludoMCDV42ybdnatSAu067