Mean Well DRH-120-24 Installation Manual

Download Installation manual of Mean Well DRH-120-24 Power Supply for Free or View it Online on All-Guides.com. This version of Mean Well DRH-120-24 Manual compatible with such list of devices, as: DRH-120-24, DRH-120-48, DRT-240-24, DRT-480-24, DRT-960-24

Mean Well DRH-120-24 Installation manual - Page 1
1
Mean Well DRH-120-24 Installation manual - Page 2
2
Mean Well DRH-120-24 Installation manual - Page 3
3
InstallationManual
TypeGeneralTypeDINrailwithThreePhaseorHighInputRange
SeriesDRH120,DRT240,DRT480,DRT960
DRH12024 INPUT:400‐500VAC0.65A50/60Hz OUTPUT:24V5A
DRH12048 INPUT:400‐500VAC0.65A50/60Hz OUTPUT:48V2.5A
DRT24024 INPUT:400‐500VAC0.95A50/60Hz OUTPUT:24V10A
DRT24048 INPUT:400‐500VAC0.95A50/60Hz OUTPUT:48V5A
DRT48024 INPUT:400‐500VAC1.7A50/60Hz OUTPUT:24V20A
DRT48048 INPUT:400‐500VAC1.7A50/60Hz OUTPUT:48V10A
DRT96024 INPUT:400‐500VAC2.4A50/60Hz OUTPUT:24V40A
DRT96048 INPUT:400‐500VAC2.4A50/60Hz OUTPUT:24V20A
Introduction
General type with three phase or high input range is a DIN rail power supply series with a high input range,
340550Vac.LikeotherMeanWell’sDINseries,theycanbemountedonaTS35StandardDINrail.
Installation
1Alwaysallowgoodventilationclearances,5mmleftandright,40mmaboveand20mmbelow,around theunit
inuse topreventitfromoverheating.Alsoa1015cmclearancemustbekeptwhentheadjacentdeviceisa
heatsource.
2Theappropriatemountingorientationfor
theunitisvertical,theinputterminalsatthebottomandoutputon
the top for DRH120, the input terminals on the right and output on the left for DRT240, DRT480 and
DRT960. Mounting orientations other than that, such as upside down, horizontal, or tabletop
mounting, is
notallowed.
3Usecopperwireonly,andrecommendedwiresareshownasbelow.
AWG 18 16 14 12 10
RatedCurrentof
Equipment(Amp)
6A 610A 1316A 1625A 2532A
Crosssectionof
Lead(mm
2
)
0.75 1.00 1.5 2.5 4
Note:Currenteachwirecarriesshouldbederatedto80%ofthecurrentsuggested
abovewhenusing5ormorewiresconnectedtotheunit.
Make surethatall strands ofeachstrandedwireenterthe terminal connectionand the screwterminals are
securely fixed to preven t poor contact. If the power supply possesses multioutput terminals, please make
sureeachcontactisconnectedtowirestopreventtoomuchcurrentstressonasinglecontact.
4Usewiresthatcanwithstandtemperaturesofatleast80°CsuchasUL1007.
5Recommendedwirestrappinglengthis5mm(0.197”).
6Recommendedscrewdriveris4mm,slottedtype.
7Therecommendedtorquesettingforterminalsis 10kgfcm(9Lbin).