Environmental Requirements and Specifications for EX Series Switches
The switch must be installed in a rack or cabinet housed in a dry, clean, well-ventilated,
and temperature-controlled environment.
Ensure that these environmental guidelines are followed:
•
The site must be as dust-free as possible, because dust can clog air intake vents and
filters, reducing the efficiency of the switch cooling system.
•
Maintain ambient airflow for normal switch operation. If the airflow is blocked or
restricted, or if the intake air is too warm, the switch might overheat, leading to the
switch temperature monitor shutting down the switch to protect the hardware
components.
Table 38 on page 85 provides the required environmental conditions for normal switch
operation.
Table 38: EX Series Switch Environmental Tolerances
Environment Tolerance
Switch or
device SeismicTemperatureRelative HumidityAltitude
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operationensuredin the
temperature range 32° F (0° C)
through 104° F (40° C) at
altitudes up to 5,000 ft
(1,524 m).
For information about extended
temperature SFP transceivers
supportedon EX2200 switches,
see Pluggable Transceivers
Supported on EX2200 Switches.
Normal operationensuredin
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
5,000 feet
(1524 meters)
EX2200-C
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operationensuredin the
temperature range 32° F (0° C)
through 113° F (45° C)
Normal operationensuredin
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet
(3048 meters)
EX2200
(except
EX2200-C
switches)
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operationensuredin the
temperature range 32° F (0° C)
through 104° F (40° C)
Normal operationensuredin
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
5,000 feet
(1524 meters)
EX2300-C
85Copyright © 2017, Juniper Networks, Inc.
Chapter 6: Preparation Overview