Table 61: Parts and Tools Required for Connecting an EX Series Switch to Earth
Ground (continued)
Additional
InformationScrewdriver
Screws and
Washers
Grounding Lug
Specifications
Grounding Cable
Requirements
Earthing
Terminal
LocationSwitch
Phillips (+)
number 2
•
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
•
Two #10 flat
washers—not
provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Rear panel
of the
chassis
EX3400
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 151.
Phillips (+)
number 2
•
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
•
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 WG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Left side of
the chassis
EX4200
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 151.
Phillips (+)
number 2
•
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
•
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Left side of
the chassis
EX4300
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 151.
Phillips (+)
number 2
•
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
•
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Left side of
the chassis
EX4500
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 151.
Phillips (+)
number 2
•
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
•
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Left side of
the chassis
EX4550
Phillips (+)
number 2
•
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer
—provided
•
Two #¼” flat
washers—
provided
Panduit
LCD2-14A-Q or
equivalent
—provided
The grounding
cable must be the
same gage as the
power feed cables
and as permitted
by the local code.
Rear panel
of the
chassis (on
lower left
side)
EX6210
149Copyright © 2017, Juniper Networks, Inc.
Chapter 12: Connecting the Switch to Power